3100 Wood Stove Series (ACC)

 

R

 

 

 

 

Mobile Home Installation

 

 

 

must use a Quadra-Fire Outside Air Kit Part

 

 

You6

 

 

 

OAK-ACC and (depending on floor installation,

 

SparkArestor Cap

Part SRV7033-041) for installation in a mobile

 

 

home.

 

 

 

1.

An outside air inlet must be provided for combustion See

Storm Collar

 

 

page 14 for installation information.

 

 

 

 

2.

Appliance must be secured to the mobile home structure

 

Roof Flashing

 

by bolting the pedestal through hearth pad and into

 

 

 

floor.

 

 

 

3.

Appliance must be grounded with #8 solid copper

 

 

 

grounding wire or equivalent and terminated at each end

Joist Shield/Firestop

Double wall

 

with N.E.C. approved grounding device.

 

 

4.

Appliance must be installed with an approved UL103 HT

 

connector pipe

 

 

 

ventilated chimney connector, UL103 HT chimney, and

 

 

 

terminal cap with spark arrestor. Never use a single wall

 

 

 

connector (stove pipe) in a mobile home installation. Use

 

 

 

only double-wall connector pipe, Dura-Vent DVL, Selkirk

 

 

 

metalbestos DS or Security DL double-wall connector or

 

 

 

any listed double-wall connector pipe.

 

 

5.

In Canada, this appliance must be connected to a 6 inch

 

OutsideAir

 

(152mm) factory-built chimney conforming to CAN/ULC-

 

RearVent

 

629M, STANDARD FOR FACTORY BUILT CHIMNEYS.

 

 

6.

Follow the chimney and chimney connector manufacturer’s

Floor Protector

 

 

instructions when installing the flue system for use in a

 

 

 

 

 

mobile home.

 

 

7.

Maintain clearance to combustibles.

 

 

8.

Floor protection requirements must be followed

Outside Air Floor Vent

 

 

precisely.

 

 

 

 

9.

Use silicone to create an effective vapor barrier at the

Figure 20.1

 

 

location where the chimney or other component penetrates

 

 

 

 

 

to the exterior of the structure.

 

 

NOTE: Offsets from the vertical, not exceeding 45°, are

CAUTION

allowed per Section 905(a) of the Uniform Mechanical Code

(UMC). Offsets greater than 45° are considered horizontal

Maintain structural integrity of mobile home:

and are also allowed, providing the horizontal run does not

• Floor, wall, ceiling and/or roof.

exceed 75% of the vertical height of the vent. Construction,

Do NOT cut through:

clearance and termination must be in compliance with the

• Floor joist, wall, studs or ceiling trusses.

UMC Table 9C. This installation must also comply with NFPA

• Any supporting material that would affect the structural

211.

integrity.

NOTE: Top sections of chimney must be removable to allow

 

 

maximum clearance of 13.5 feet (411cm) from ground level

 

for transportation purposes.

 

WARNING

10. Burn wood only. Other types of fuels may generate

poisonous gases (e.g., carbon monoxide).

 

Asphyxiation Risk.

11. If unit burns poorly while an exhaust blower is on in

• Never install in a sleeping room.

home, (i.e., range hood), increase combustion air.

Consumes oxygen in the room.

 

12.Installation shall be in accordance with the Manufacturers Home & Safety Standard (HUD) CFR 3280, Part 24.