F. Junction Box Installation

If the box is being wired from the OUTSIDE of the appli- ance:

Remove the cover plate located on the outer shell - right side (see Figure 12.4).

Install the supplied Romex™ connector in the cover plate.

If the box is being wired from the INSIDE of the appli- ance:

Remove the screw attaching the junction box/receptacle to the outer shell, rotate the junction box inward to disengage it from the outer shell (see Figure 12.4).

Pull the electrical wires from outside the appliance through this opening into the valve compartment. See Figure 12.4.

G. Wall Switch Installation for Fan (Optional)

If the box is being wired to a wall mounted switch for use with a fan (See Figure 12.5):

The power supply for the appliance must be brought into a switch box.

The power can then be supplied from the switch box to the appliance using a minimum of 14-3 with ground wire.

At the switch box connect the black (hot) wire and red (switch leg) wire to the wall switch as shown.

At the appliance connect the black (hot), white (neutral) and green (ground) wires to the junction box as shown.

Add a 1/4 in. insulated female connector to the red (switch leg) wire, route it through the knockout in the face of the junction box, and connect to the top fan switch connector (1/4 in. male) as shown.

Romex

Connector

14/2WG

Cover Plate outside firebox

WHT

BLK

WHT

 

BLK

Copper

GRN wire

ground attached

inside box

to GRN screw with

 

GRN wire

NOTICE: DO NOT wire 110 VAC to wall switch.

Figure 12.4 Junction Box Detail

Minimum 14-3 AWG

 

Switch

 

 

with Ground

 

 

 

Red

 

 

Black

Black

 

White

White

Junction Box

Green

Green

Red Black White Green

 

Power

 

Switch Box

 

Supply

 

 

 

 

Wires

 

Knockout

 

Red

 

 

Figure 12.5 Junction Box Wired to Wall Switch or BC10

44

Heatilator • Eclipse • 4049-229 Rev F • 11/08

Page 44