Heatilator • Eclipse • 4049-229 Rev F • 11/0830
WALL
No combustible
framing to be
located within
shaded area.
2 x 4 or
2 x 6
header
Drywall
3 in.
(76 mm)
1 in. (25 mm)
3/4 in. (19 mm)
minimum to
perpendicular
wall.
Air space clearance to
bottom and sides of
horizontal pipe must be
at least 1 in. (25 mm)
Note: Heat shields MUST overlap by a minimum of 1 1/2 in. (38 mm).
SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8
in. (111 mm to 194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must
be field trimmed. If wall thickness is greater than 7-5/8 in. an
extended heat shield will be required.
*When using SLP pipe, minimum clearances from the vent pipe to
combustible materials at inside wall firestops are:
Top: 2-1/2 in. (64 mm)
Bottom: 1/2 in. (13 mm)
Sides: 1 in. (25 mm)
Framing should be
constructed of 2 X 4
lumber or heavier.
The center of the
framing hole is
1 in. [25mm] above
the center of the
horizontal vent pipe.
Vent
framing
hole
36 1/2 in. [927 mm]
(Center of pipe)
10 in.
[254mm]
10 in.
[254mm]

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
Between ceiling restops
• Between wall shield restops
• Around vent system
Failure to keep insulation or other material away from vent
pipe may cause over heating and re.
8
8 Vent Clearances and Framing
Figure 8.2 Wall Penetration
Figure 8.1 Horizontal Venting Clearances To Combustible Materi-
als

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield restops. A wall shield
restop maintains minimum clearances and prevents cold
air in ltration.
The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
A wall shield restop must be placed on each side of
an interior wall. A minimum 1 1/2 in. (38 mm) overlap of
attached heat shields must be maintained.
See Section 10.L. for information for regarding the
installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield restop is only required on one side and no heat
shield is necessary.