Seal flashing to exterior of building using hightemp caulk. Attach to building using holes provided on the top of the left and right sides of outdoor flashing (see Figure 5.15).
Í Apply housewrap or building paper
For placement of combustible housewrap or building paper and
Special care should be taken when choosing building materials for weather proofing (i.e. building wraps, seal- ant tapes, liquid sealants, rubberized flashings, etc.). All sealant materials or building wraps installed within 6 inch- es of the top and sides of the fireplace surround must be approved to a minimum temperature of 225° F continuous exposure. Consult the material’s manufacturer to ensure product compliance.
TOP OF SURROUND | METAL FLASHING |
| |
| 6 IN. |
EDGE OF SURROUND | 6 IN. |
| |
Í Figure 5.16 Outside View without |
| SHEATHING, | |
| COMBUSTIBLE | |
WALL STUD | HOUSEWRAP ** | |
| (BUILDING | |
| PAPER) OVERLAP | |
| FLASHING 1 in. | |
FIREPLACE |
| |
HEADER |
| |
HOUSEWRAP | ||
| SHEATHING | |
INSULATION | 12 in. | |
| ||
FLASHING | TOP OF | |
FIREPLACE | ||
HEADER |
| |
INSULATED | ||
FRAMING |
| |
STANDOFF |
| |
| TOP HOOD | |
| APPLIANCE | |
| HOOD | |
Figure 5.17 |
|
*NOTE: All finishing materials on top of exterior sheathing must be
** NOTE: Combustible house wrap or building paper | Í |
MUST NOT extend over the outside of |
|
sheathing, and MAY extend over the flashing behind non- |
|
combustible sheathing. Use high temp silicone or sealant |
|
recommended by the manufacturer of the housewrap to |
|
seal between combustible sheathing house wrap and non- |
|
combustible sheathing. The sealant material used within |
|
6 inches of the top and sides of the fireplace surround |
|
must be approved to a minimum temperature of 225° F |
|
continuous exposure. |
|
Once the appliance is in place use enough high tempera- ture silicone sealant or manufacturer specified sealant (approved to a minimum of 225° F) to make a water tight seal between outdoor surround and exterior sheathing.
Face the perimeter of the appliance with
| |
ZONE |
|
12 in. | 12 in. |
| 12 in. |
Figure 5.18 |
|
WARNING
Risk of Fire
•
• Sheetrock, wood or other combustibles must NOT be used as sheathing or facing in the
•See Sections 3 and 8 for proper clearances.
•See Section 1 for