8 Finishing

A. Mantel Projections

Figure 8.1 shows the minimum vertical and corresponding maximum horizontal dimensions of appliance mantels or other combustible projections above the top front edge of the appliance.

Interior

 

CEILING

View

 

 

 

NON-COMBUSTIBLE BOARD

 

(SUPPLIED ON APPLIANCE)

 

 

INDOOR SIDE ONLY

 

 

 

12

 

10

11

 

35-3/4

 

9

 

 

 

8

 

 

7

13-5/8

 

6

12-5/8

 

11-5/8

 

10-5/8

 

 

9-5/8

 

 

8-5/8

 

HOOD

7-5/8

 

 

Note: Measurements

 

are in inches.

Figure 8.1 Indoor Clearances to Mantels or other

Combustibles above Appliance

 

Top View

MEASURED

FROM CORNER

Inside Facing Material

May install combustible materials up to specified clearances on top, front and sides of appliance.

Seal joints between finished wall and appliance top and sides with 300º F (140º C) minimum sealant.

Leave space so bottom grille can be lowered for trim door removal.

NON-COMBUSTIBLE ZONE

 

 

 

 

 

 

 

 

 

 

 

 

 

41-7/8 in.

 

 

 

 

 

 

 

 

 

2-3/4 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8.3 Non-combustible Zone (Interior)

Outside Facing Material

OVERHANG

FIREPLACE

HOOD

½ IN.

A

SIDING

A

B

 

 

 

A

Figure 8.2 Clearances to Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening.)

B. Facing Material

WARNING

Fire Risk.

Do NOT obstruct air inlet or outlet grilles. Do NOT modify grilles.

• Modifying or covering grilles could cause temperature rise and fire hazard.

Finishing materials must not interfere with:

Air flow through grilles or louvers.

Operation of louvers or doors.

Access for service.

SIDING

SIDING

 

Vinyl

Non-vinyl

A

36 in.

12 in.

B

64-5/16 in.

35-5/16 in.

Figure 8.4 Exterior View - Minimum Clearances