Page 22 Heat & Glo • NorthStar EPA Fireplace • 480-1081C September 1, 2008 September 1, 2008
September 1, 2008
D. Assemble the Chimney Sections
Attach either a straight chimney section or an offset to the
topofthereplace (dependingonyourinstallation require-
ment). Chimney sections are locked together by pushing
downward until the top section meets the stop bead on the
lower section.
Theinnerueisplacedtotheinsideoftheuesectionbelow
it. The outer casing is placed outside the outer casing of the
chimney section below it. See Figure 22.1.
If you are using a different approved venting system, follow
the instructions that were supplied with that system.
Note: In ner flue and out er liner sec tions can not be
disassembled once locked together. Plan ahead to ensure
the proper installation height is achieved with the selected
chimney components.
Figure 22.1 Assembling Chimney Sections
Fire Risk
DoNOT install substitute or damaged
chimney components.
• MUSTusechimneysystemdescribedin
this manual.
• NO OTHER chimney components may
be used.
Substitute or damaged chimney components
may impair safe operation.
WARNING
E. Assembling Chimney Sections for the SL-300 Series
NOTE: Chimney Air Kit, Part CAK4A is REqUIRED
when using the SL-300 Pipe Series. Detailed instruc-
tions are supplied with the kit.
Attach
Flue First
CAK4A
Secure with Screws
Provided
Push Together
Secure to Top
Installing CAK4A and Flex Pipe
NOTE: FOLLOW DETAILED INSTRUCTIONS THAT COME
WITH THE CAK4A.
1. Installthechimneypiperst.
2. Hand bend the tabs in position before placing on the
replace.
3. Placetheboxontopofthereplacearoundthechimney
pipe, push both pieces together and secure with screws
provided.
4. Use the pre-punched holes in the tabs as guides and drill
holesthroughthereplacetop.
5. Secure the CAK4A in place.
6. Sealaroundthekitatthe ueandatthetopof thecan
with caulk.
NOTES:
1. The outside termination cap must be a minimum of 6 ft
(1829 mm) above the ground and kept free of debris.
2. If the CAK4A is installed in a chase, the CAK4A side
termination cap must be at least 3 ft (914 mm) below the
chimney top.
3. Sealaroundthecapandexwithcaulk tostopairfrom
getting in to the chase (See Figure 23.1 on page 23).
Figure 22.2 Installing the CAK4A
Fire Risk
 Theexhosemustneverbe
compressed or deformed!
WARNING