Hearth and Home Technologies NorthStar-NT Complete the Enclosure, Chimney Termination 2-10-3 Rule

Models: NorthStar-GT NorthStar-BK NorthStar-NT

1 72
Download 72 pages 45.16 Kb
Page 25
Image 25

6 Complete the Enclosure

A. Chimney Termination (2-10-3 Rule)

Chimney Termination Requirements (See Figures 25.1 and 25.2)

Must have a cap approved and listed for this fireplace system

Must not be located where it will become plugged by snow or other material

Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft (3.05 m)

Must be located away from trees or other structures

Slanted Roofs

Chimney must extend 3 ft (914 mm) above the roof

Chimney must extend 2 ft (610 mm) above any portion of the roof

within 10 ft (3048 mm) of the chimney

Flat Roofs

Chimney must extend 3 ft (914 mm) above the roof

Chimney must extend 2 ft (610 mm) above any portion of the roof

within 10 ft (3048 mm) of the chimney

Figure 25.1 Termination Requirements

GAS, WOOD OR FUEL

OIL TERMINATION

GAS C TERMINATION

B

A

 

Gas

Wood & Fuel Oil

Comments

 

Termination

Termination

 

 

 

 

 

 

A

6 in.

20 in. min.

Horizontal distance between terminations

 

 

 

 

B

20 in.

24 in. min.

Distance to perpendicular wall

C

18 in.

18 in.

Vertical distance between terminations

 

 

 

 

Figure 25.2 Multiple Chimneys

September 1, 2008

Heat & Glo • NorthStar EPA Fireplace • 480-1081C

Page 25

Page 25
Image 25
Hearth and Home Technologies NorthStar-NT Complete the Enclosure, Chimney Termination 2-10-3 Rule, Slanted Roofs