F. Horizontal Termination

TERMINATION CAP

90º ELBOW

PIPE LENGTH

WALL THIMBLE

WALL THIMBLE COVER

PIPE LENGTH

CHOOSE BETWEEN

SLIM LINE

OR

STANDARD

WALL THIMBLE

WALL THIMBLE

INTERIOR WALL

-2 IN. (51 MM)

CLEARANCE FROM REAR OF STOVE

CENTER LINE SNORKEL CAP

MINIMUM OF 6 IN. (152 MM) OF

PIPE THROUGH THE WALL

TRIM RING

SNORKEL CAP KIT (SLK-SNKD) MUST BE

USED FOR HORIZONTAL VENT RUNS

WITH NO VERTICAL RISE.

Figure 5.3

1.Determine the desired location of the appliance. Check to ensure that wall studs or roof rafters are not in the way when the venting system is being planned. If this is the case, you may want to adjust the location of the appliance.

WARNING

Fire Risk

Exhaust Fumes Risk

Impaired Performance of Appliance

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

2.Direct vent pipe is designed with a locking connection. To connect the venting system to the appliance flue outlet, a twist-lock adapter is built into the appliance at the factory. Wall thickness may vary. Remember to include wall thickness in minimum clearances when figuring venting lengths for your installation needs.

3.Female ends of direct vent pipe/elbows are designed to slide straight onto the male ends of adjacent pipes by orienting the pipe indentations so they match and slide into the entry slots on the male ends, see Figure 5.4. Push the pipe sections completely together, then twist-lock one section clockwise approximately one- quarter turn, until the two sections are fully locked. The female locking lugs may not be visible from the outside. They may be located by examining the inside of the female ends.

FEMALE LOCKING LUGS

MALE LOCKING

Figure 5.4

WARNING

Fire Risk. Explosion Risk. Combustion Fume Risk.

Use vent run supports per installation instructions.

Connect vent sections per installation instructions.

Maintain all clearances to combustibles.

Do NOT allow vent to sag below connection point to appliance.

Maintain specified slope (if required). Improper support may allow vent to sag or separate.

4.For installations using a round support box/wall thimble (check pipe manufacturer's instructions), mark the wall for a 10 in. x 10 in. (254 mm x 254 mm) square hole. The center of the square hole should line up with the center line of the horizontal pipe, as shown in Figure 5.5. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or concrete, a 7 in. (178 mm) diameter hole is acceptable.

Heat & Glo • Paloma • 7031-220 Rev. P • 10/08

13

Page 13
Image 13
Hearth and Home Technologies PALOMA-BL, PALOMA-GR, PALOMA-BZ Horizontal Termination, Female Locking Lugs Male Locking