Heat & Glo LifeStyle SUPREME-P-I30AU Must adhere to pipe clearances Colinear to Coaxial Adapter

Models: SUPREME-P-I30AU SUPREME-N-I30AU

1 60
Download 60 pages 51.13 Kb
Page 30
Image 30

Note: The header can only be installed in an existing masonry chase or equivalent non-combustible enclosure. Clearances around and above pipe must be adhered to.

Note: Adhere to AS5601 plumbers code for minimum clearances for termination of balanced flue appliances.

11-7/8 in.

(600 mm)

MAXIMUM

SLP-TRAP

10 ft. (3 m)

MINIMUM

SLP 90° BEND

Must adhere to pipe clearances.

Colinear to Coaxial Adapter

LINK ADAPTER

225 & 275 Ø

GALVANIZED FLUE

NOTE: Any 3 in. (76 mm) section of flex pipe must be enclosed to existing fireplace flue in double lined flue to comply with AS2918-2001 and the building code of Australia.

Seal connection points for ducting. Sealant must have a minimum ex- plosure rating of 649 °C (1200 °F).

NOTE: Tape all SLP pipe connec- tions with aluminum foil tape rated to a minimum of 149 °C (300 °F).

FLEXIBLE FLUE MIN. 35-7/16 ft. (900 mm)

STARTER PLATE

Figure 8.13 Optional SLP venting configuration - Horizontal Termination

30

Heat & Glo • Supreme-N-I30AU, Supreme-P-I30AU2222-900 Rev. P • 6/12