Chapter 6 OPERATION
(Note 6) : If satisfactory performance can not be obtained, adjust the motor constants for the particular symptoms observed according to following table:
Inverter | Symptom Observed | Adjustment Guidelines | Parameter(s) | ||||
Status | to Adjust | ||||||
|
|
|
|
| |||
At starting | Shock | occurs | at | Set “Motor constant J” higher gradually, up to | H024/H034 | ||
| starting |
|
|
| 1.2 times the initially preset (default) value. |
| |
At | Instability of | motor | Set the speed response lower. | H005 | |||
|
| ||||||
deceleratio | rotation |
|
|
| Set “Motor constant J” smaller than the | H024/H034 | |
n |
|
|
|
| initially preset value. |
| |
During | Insufficient | torque | Set overload restriction level lower than the | b022 | |||
torque limit | during | torque | limit | torque limit level(s). | |||
| at low speed |
|
|
|
| ||
At low | Irregular rotation | Set “Motor constant J” higher than the initial | H024/H034 | ||||
frequency | |||||||
operation |
|
|
|
| preset (default) value. |
| |
|
|
|
|
|
|