Chapter 6 OPERATION

(Note 6) : If satisfactory performance can not be obtained, adjust the motor constants for the particular symptoms observed according to following table:

Inverter

Symptom Observed

Adjustment Guidelines

Parameter(s)

Status

to Adjust

 

 

 

 

 

At starting

Shock

occurs

at

Set “Motor constant J” higher gradually, up to

H024/H034

 

starting

 

 

 

1.2 times the initially preset (default) value.

 

At

Instability of

motor

Set the speed response lower.

H005

 

 

deceleratio

rotation

 

 

 

Set “Motor constant J” smaller than the

H024/H034

n

 

 

 

 

initially preset value.

 

During

Insufficient

torque

Set overload restriction level lower than the

b022

torque limit

during

torque

limit

torque limit level(s).

b041-b044

 

at low speed

 

 

 

 

At low

Irregular rotation

Set “Motor constant J” higher than the initial

H024/H034

frequency

operation

 

 

 

 

preset (default) value.

 

 

 

 

 

 

 