Chapter 8 PROTECTION FUNCTION

8.1 Action selection in case of option error

To ignore or make inverter trip can be selected in case of option error.

Item

Function code

Data

Contents

Action selection in

P001 / P002

00

TRP: Inverter trips and outputs alarm signal.

 

RUN: Inverter ignores the option error and

case of option error

01

 

continues the operation.

 

 

 

(Note) : Inverter trips anyway in case of encoder line break error (E60, E70), SJ-FB abnormal connection (E69,E79) occurs, although action selection is set to 01 (RUN). Please refer to "Chapter 5.2 FEED-BACK BOARD INITIAL SETTINGS".

8.2 Causes and Countermeasures for Option Board Errors

When any of the following alarms occurs, the inverter displays the alarm cause and stops.

Display

Item

Contents

Processing

 

 

Detect the line break or disconnection of the

Check the encoder signal line and

E60

 

encoder line.

connection.

Encoder line

Detect when there is an encoder failure.

Replace it to a suitable one.

(E70)

break

Detect when the specification of the encoder is

(Note 1)

not line driver output type.

 

 

 

 

 

Detect when there is no Z pulse.

Turn SWENC-2 OFF on the option

 

 

board.

 

 

 

E61

 

Detect when the motor rotation speed exceeds

Adjust the Kp and J constants

Over speed

(maximum frequency (note 2))×(over speed

(E71)

error detection level (P026).

related to the speed control system

(Note 1)

 

to reduce overshoot.

 

 

(Note 3),(Note 4)

 

E62

 

Detect when the deviation of the current

Increase the position loop gain.

(E72)

Positioning

position and command value becomes more

Decrease the numbers of the pulse

(Note 1)

error

than 1,000,000 pulses during position

train input per second.

 

 

controlling.

 

E69

connection

Detect abnormal connection between the

Check the connection between the

(E79)

error

inverter main body and SJ-FB.

inverter main body and SJ-FB.

(Note 1)

 

 

 

(Note 1): Data in parentheses ( ) applies when the option card is connected to option slot 2.

(Note 2): Frequency upper limit value (A061/A261) is reflected when it is set.

(Note 3): It depends on what type of main body combines with the SJ-FB, the setting value conversion is different.

Please refer to the (Note 3) of the “5.3 Items regarding the feed back board of the inverter main body“.

(Note 4): When the over speed error occurred . There is a possibility the over speed error occur again. Even though the trip is cleared during the motor free run. In this case stop the motor, then clear the trip please.

8.3 Warning display (Feed back option relation)

(Refer to the operation manual of the main body about the warning other than the following,)

The 009 is displayed in the case that it became orientation speed setting (P015) > the highest