| | | | | | | | [◯= Allowed×= Not permitted | | ] |
| | | | | | | | |
| | | | | | | | | | | | | | | |
| Code | Function Name | Monitored data or setting | | Default Setting | Setting | Change | |
| | | SJ700 | | SJ700B | during operation during operation | | | |
| | | | | -FE(CE) -FU(UL) | -F(JP) | (allowed or not) | (allowed or not) | |
| and | b028 | Active frequency matching, scan start frequency | SJ700: 0.20 x "rated current" to 2.00 x "rated current" (A) < 75kW and over:0.20 x 1.50 > | Rated current of inverterx 1..0 | × | ○ |
| restraint | SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A) |
| restriction | | | | | | | | | | | | | | |
| overcurrent | b029 | Active frequency matching, scan-time constant | 0.10 to 30.00 (s) | 0.50 | | 0.50 | 0.50 | 0.50 | × | ○ |
| Overload | |
| b030 | Active frequency matching, restart frequency select | 00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set frequency) | 00 | | 00 | 00 | 00 | × | ○ | | | |
| software | | | 00 (disabling change of data other than "b031" when SFT is on), 01 (disabling change | | | | | | | | | | | |
| | | of data other than "b031" and frequency settings when SFT is on), 02 (disabling change | | | | | | | | | | | |
| lock | b031 | Software lock mode selection | 01 | | 01 | 01 | 01 | × | ○ |
| of data other than "b031"), 03 (disabling change of data other than "b031" and | |
| | | | frequency settings), 10 (enabling data changes during operation) | | | | | | | | | | | |
| | b034 | RUN/ power-on warning time | 0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr) | 0. | | 0. | 0. | 0. | × | ○ | | | |
| | b035 | Rotational direction restriction | 00 (enabling both forward and reverse rotations), 01 (enabling only forward rotation), | 00 | | 00 | 00 | 00 | × | × | | | | |
| | 02 (enabling only reverse rotation) | | | | | |
| Others | | | | | | | | | | | | | |
| b036 | Reduced voltage start selection | 0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time) | 06 | | 06 | 06 | 06 | × | ○ | | | |
| b037 | Function code display restriction | 00 (full display), 01 (function-specific display), 02 (user setting), 03 (data comparison | 04 | | 04 | 04 | 04 | × | ○ | |
| display), 04 (basic display) | |
| | b038 | Initial-screen selection | 00 (screen displayed when the STR key was pressed last), 01 (d001), 02 (d002), | 01 | | 01 | 01 | 01 | × | ○ |
| | 03 (d003), 04 (d007), 05 (F001) | |
| | | | | | | | | | | | | | |
| | b039 | Automatic user-parameter setting function enable | 00 (disabling), 01 (enabling) | 00 | | 00 | 00 | 00 | × | ○ | | | |
| | b040 | Torque limit selection | 00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog input), 03 (option 1), | 00 | | 00 | 00 | 00 | × | ○ | |
| | 04 (option 2) | |
| limitation | b042 | Torque limit(1) | SJ700: 0. to 200. (%), no (disabling torque limitation) < 75kW and over:0. to 180.> | 150. | | 150. | 150. | 120. | × | ○ |
| (Reverse-regenerating in 4-quadrant mode) | SJ700B: 0. to 150.(%), no (disabling torque limitation) | |
| | b041 | (Forward-driving in 4-quadrant mode) | SJ700B: 0. to 150.(%), no (disabling torque limitation) | 150. | | 150. | 150. | 120. | × | ○ |
| Torque | | Torque limit(2) | SJ700: 0. to 200. (%), no (disabling torque limitation) < 75kW and over:0. to 180.> | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | b043 | Torque limit(3) | SJ700: 0. to 200. (%), no (disabling torque limitation) < 75kW and over:0. to 180.> | 150. | | 150. | 150. | 120. | × | ○ | |
| | (Reverse-driving in 4-quadrant mode) | SJ700B: 0. to 150.(%), no (disabling torque limitation) | |
| | b044 | Torque limit(4) | SJ700: 0. to 200. (%), no (disabling torque limitation) < 75kW and over:0. to 180.> | 150. | | 150. | 150. | 120. | × | ○ |
| | (Forward-regenerating in 4-quadrant mode) | SJ700B: 0. to 150.(%), no (disabling torque limitation) | |
| | b045 | Torque limit LADSTOP enable | 00 (disabling), 01 (enabling) | 00 | | 00 | 00 | 00 | × | ○ | | |
| failure | b046 | Reverse RUN protection enable | 00 (disabling), 01 (enabling) | 00 | | 00 | 00 | 00 | × | ○ | | |
| b050 | Controlled deceleration and stop on power loss | 00 (disabling), 01 (enabling) | 00 | | 00 | 00 | 00 | × | × | | | | |
at | | | | | | | | | | | | | | |
operation | | | | | | | | | | | | | |
b052 | Over-voltage threshold during power loss | 0.0 to 999.9, 1000. (V) | 360.0/720.0 | 360.0/720.0 | 360.0/720.0 | 360.0/720.0 | × | × | | | | |
| power | b051 | DC bus voltage trigger level during power loss | 0.0 to 999.9, 1000. (V) | 220.0/440.0 | 220.0/440.0 | 220.0/440.0 | 220.0/440.0 | × | × | | | | |
| | | | | | | | | | | | | | |
| momentary | | | | | | | | | | | | | | |
stop-Non | | | | | | | | | | | | | | |
| | b053 | Deceleration time setting during power loss | 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) | 1.00 | | 1.00 | 1.00 | 1.00 | × | × | | | | |
| | b054 | Initial output frequency decrease during power loss | 0.00 to 10.00 (Hz) | 0.00 | | 0.00 | 0.00 | 0.00 | × | × | | | | |
| | b055 | Proportional gain setting for nonstop operation at power loss | 0.00 to 2.55 | 0.20 | | 0.20 | 0.20 | 0.20 | ○ | ○ | |
| | b056 | Integral time setting for nonstop operation at power loss | 0.0 to 9.999 /10.00 to 65.55 | 0.100 | | 0.100 | 0.100 | 0.100 | ○ | ○ | |
| | b060 | Maximum-limit level of window comparators O | 0. to 100. (lower limit : b061 + b062*2) (%) | 100 | | 100 | 100 | 100 | ○ | ○ | | |
| comparator | b061 | Minimum-limit level of window comparators O | 0. to 100. (lower limit : b060 - b062*2) (%) | 0 | | 0 | 0 | 0 | ○ | ○ | | |
| b065 | Hysteresis width of window comparators OI | 0. to 10. (lower limit : b063 - b064 / 2) (%) | 0 | | 0 | 0 | 0 | ○ | ○ | | |
| | b062 | Hysteresis width of window comparators O | 0. to 10. (lower limit : b061 - b062 / 2) (%) | 0 | | 0 | 0 | 0 | ○ | ○ | | |
| | b063 | Maximum-limit level of window comparators OI | 0. to 100. (lower limit : b064 + b066*2) (%) | 100 | | 100 | 100 | 100 | ○ | ○ | |
| | b064 | Minimum-limit level of window comparators OI | 0. to 100. (lower limit : b063 - b066*2) (%) | 0 | | 0 | 0 | 0 | ○ | ○ | |
| Window | | | | | | | | | | | | |
| b066 | Maximum-limit level of window comparators OI | -100. to 100. (lower limit : b067 + b068*2) (%) | 100 | | 100 | 100 | 100 | ○ | ○ |
| b068 | Hysteresis width of window comparators O/OI/O2 | 0. to 10. (lower limit : b066 - b067 / 2) (%) | 0 | | 0 | 0 | 0 | ○ | ○ | |
| | b067 | Minimum-limit level of window comparators O/OI/O2 | -100. to 100. (lower limit : b066 - b068*2) (%) | -100 | -100 | -100 | -100 | ○ | ○ | |
| | | | | | | | | | | | |
| | b070 | Operation level at O disconnection | 0 to 100 (%) or "no" (ignore) | 255(no) | 255(no) | 255(no) | 255(no) | × | ○ |
| | b071 | Operation level at OI disconnection | 0 to 100 (%) or "no" (ignore) | 255(no) | 255(no) | 255(no) | 255(no) | × | ○ | |
| | b072 | Operation level at O2 disconnection | 0 to 100 (%) or "no" (ignore) | 127(no) | 127(no) | 127(no) | 127(no) | × | ○ | |
| | b078 | Cumulative input power data clearance | Clearance by setting "01" and pressing the STR key | 00 | | 00 | 00 | 00 | ○ | ○ | |
| | b079 | Cumulative input power display gain setting | 1. to 1000. | 1. | | 1. | 1. | 1. | × | × | | | | |
| | b082 | Start frequency adjustment | 0.10 to 9.99 (Hz) | 0.50 | | 0.50 | 0.50 | 0.50 | × | ○ | |
| | b083 | Carrier frequency setting | SJ700: 0.5 to 15.0(kHz) <75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0> | 5.0(*2) | 5.0(*2) | 5.0(*2) | 3.0(*1) | × | × | | | | |
| | SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0.> | | | | |
| | | | | | | | | | | | | | |
| | b084 | Initialization mode (parameters or trip history) | 00 (clearing the trip history), 01 (initializing the data), 02 (clearing the trip history and | 00 | | 00 | 00 | 00 | × | × | | | | |
| | initializing the data) | | | | | |
| | | | | | | | | | | | | | |
| | b085 | Country code for initialization | 00 (Japan), 01 (EU), 02 (U.S.A.) | 01 | | 02 | 00 | 01 | × | × | | | | |
| | b086 | Frequency scaling conversion factor | 0.1 to 99.0 | 1.0 | | 1.0 | 1.0 | 1.0 | ○ | ○ | |
| Others | b087 | STOP key enable | 00 (enabling), 01 (disabling), 02 (disabling only the function to stop) | 00 | | 00 | 00 | 00 | × | ○ | |
| b088 | Restart mode after FRS | 00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting with active | 00 | | 00 | 00 | 00 | × | ○ |
| matching frequency) | |
| | |
| | | | | | | | | | | | | | |
| | b089 | Automatic carrier frequency reduction | 00: invalid, 01: valid | 00 | | 00 | 00 | 00 | × | × | | | | |
| | b090 | Dynamic braking usage ratio | 0.0 to 100.0 (%) | 0.0 | | 0.0 | 0.0 | 0.0 | × | ○ | |
| | b091 | Stop mode selection | 00 (deceleration until stop), 01 (free-run stop) | 00 | | 00 | 00 | 00 | × | ○ | |
| | b092 | Cooling fan control | 00 (always operating the fan), 01 (operating the fan only during inverter operation | 00 | | 00 | 00 | 00 | × | ○ | |
| | [including 5 minutes after power-on and power-off]) | |
| | b095 | Dynamic braking control | 00 (disabling), 01 (enabling [disabling while the motor is topped]), 02 (enabling [enabling | 00 | | 00 | 00 | 00 | × | ○ |
| | also while the motor is topped]) | |
| | | | | | | | | | | | | | |
| | b096 | Dynamic braking activation level | 330 to 380, 660 to 760(V) | 360/720 | 360/720 | 360/720 | 360/720 | × | ○ | |
| | b098 | Thermistor for thermal protection control | 00 (disabling the thermistor), 01 (enabling the thermistor with PTC), | 00 | | 00 | 00 | 00 | × | ○ |
| | 02 (enabling the thermistor with NTC) | |
| | | | | | | | | | | | | | |
| | b099 | Thermal protection level setting | 0. to 9999. (Ω) | 3000. | | 3000. | 3000. | 3000. | × | ○ | |
| characteristic | b100 | Free-setting V/f frequency (1) | 0. to "free-setting V/f frequency (2)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| b104 | Free-setting V/f frequency (3) | 0. to "free-setting V/f frequency (4)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| | b101 | Free-setting V/f voltage (1) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |
| | b102 | Free-setting V/f frequency (2) | 0. to "free-setting V/f frequency (3)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| | b103 | Free-setting V/f voltage (2) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |
| ofV/f | | | | | | | | | | | | | | |
| b105 | Free-setting V/f voltage (3) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |
| b106 | Free-setting V/f frequency (4) | 0. to "free-setting V/f frequency (5)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| setting | b107 | Free-setting V/f voltage (4) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |
| | b108 | Free-setting V/f frequency (5) | 0. to "free-setting V/f frequency (6)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| Free | b109 | Free-setting V/f voltage (5) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |
| | b110 | Free-setting V/f frequency (6) | 0. to "free-setting V/f frequency (7)" (Hz) | 0. | | 0. | 0. | 0. | × | × | | | | |
| | b111 | Free-setting V/f voltage (6) | 0.0 to 800.0 (V) | 0.0 | | 0.0 | 0.0 | 0.0 | × | × | | | | |