Hoshizaki KM-1301SRH/3, KM-1301SAH/3, KM-1301SWH/3 dPump-OutCycle, eHarvest Cycle, fShutdown

Models: KM-1301SWH/3 KM-1301SRH/3 KM-1301SAH/3

1 84
Download 84 pages 2.34 Kb
Page 19
Image 19

deenergize. For the first 5 minutes, CB will not accept a signal from F/S. This minimum 5-minute freeze time is short cycle protection for Comp. At the end of 5 minutes, F/S assumes control. As ice builds on the evaporator, the water level in the tank lowers. The freeze cycle continues until F/S opens and terminates the cycle. There is a 15 second delay before CB acknowledges an open F/S.

d)Pump-Out Cycle

LEDs 1, 3, and 2 are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on.

CAUTION! Do not adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this position on this model prevents the unit from operating correctly and may cause damage. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)." Comp and FMR remain energized, HGV energizes, WV energizes if S4 dip switch 3 off and 4 on. LLV and FM deenergize. PM stops for 2 seconds then reverses, taking water from the bottom of the tank and forcing pressure against the check valve seat allowing water to go through the check valve and down the drain. At the same time, water flows through the small tube to power flush F/S. When the pumpout timer expires, the pump-out is complete.

The first pump-out occurs after the 11th freeze cycle, then every 10th cycle thereafter. The pump-out frequency control is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 & 6) can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. Timing of the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below. For details, see "II.C.3.d) PumpOut Frequency Control (S4 dip switch 5 & 6)."

S4 Dip Switch Setting

Pump-Out

1st Pump-Out

No. 5

No. 6

Frequency

 

 

 

 

 

OFF

OFF

Every cycle

After 2nd freeze cycle

 

 

 

 

ON

OFF

Every 2 cycles

After 3rd freeze cycle

OFF

ON

Every 5 cycles

After 6th freeze cycle

 

 

 

 

ON

ON

Every 10 cycles

After 11th freeze cycle

 

 

 

 

e)Harvest Cycle

Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."

Note: Unit continues to cycle until BC is satisfied or power is turned off. The unit always restarts at the 1-minute fill cycle.

f)Shutdown

When ice contacts the thermostatic bulb (BC switch open), BC shuts down the unit within 10 seconds. The bin control is factory set, and generally no adjustment is required. However, adjustment may be needed in some conditions, particularly at higher altitude locations.

Legend: BC–bin control; CB–control board; Comp–compressor; FMR–fan motorremote; FM–fan motor; F/S–float switch; HGV–hot gas valve; LLV–liquid line valve; PM–pump motor; WV–inlet water valve