Hoshizaki KM-1301SAH/3, KM-1301SRH/3, KM-1301SWH/3 service manual

Models: KM-1301SWH/3 KM-1301SRH/3 KM-1301SAH/3

1 84
Download 84 pages 2.34 Kb
Page 51
Image 51

5)Freeze Cycle – LED 1 is on. Comp and FMR remain energized, PM energizes or remains energized depending on harvest pump timer (S4 dip switch 7) setting. FM and LLV energize. HGV, and X1 relay (auxiliary code T0, U-0), X10 relay (auxiliary code U1 and later) deenergize. The unit is held in freeze by a 5-minute short cycle protection timer (CB will not accept a signal from F/S). After the 5-minute short cycle protection timer expires, CB turns freeze termination over to F/S. During the first 5 minutes of freeze, confirm that the evaporator temperature drops. After

5 minutes in freeze, disconnect black F/S connector from CB BLACK K5 connector. After a 15 second delay, the unit should switch out of the freeze cycle. Diagnosis: If the evaporator is not cold, check to see if HGV is still open or if TXV is not opening properly, if WV is continuing to fill the reservoir, if there are improper unit pressures, an inoperative Comp, or an inoperative HM. If the unit switches out of freeze with F/S connector removed, but would previously not switch out of freeze with F/S connected (long freeze - 3 beep alarm), F/S may be sticking. To check and clean F/S, see "IV. D. Float Switch Check and Cleaning." If the unit remains in freeze longer than 15 seconds after disconnecting black F/S connector, replace CB. See "V.P. Removal and Replacement of Control Board."

Note: Normal freeze cycle will last 20 to 40 minutes depending on model and conditions. Cycle times and pressures should follow performance data provided in this manual. See "III.C. Performance Data."

6)Pump-Out Cycle – (10/20 second pump-out) – LEDs 1, 3, and 2 are on. LED 4 is on when S4 dip switch 3 & 4 are set to 3 off and 4 on. CAUTION! Do not adjust S4 dip switch 3 & 4 to 3 off and 4 on. Adjustment to this position on this model prevents the unit from operating correctly and may cause damage. For details, see "II. C.3.c) PumpOut Timer (S4 dip switch 3 & 4)." Comp and FMR remain energized, HGV energizes. WV energizes if S4 dip switch 3 off and 4 on. LLV and FM deenergize.

PM stops for 2 seconds, then reverses for 10/20 seconds depending on pumpout timer S4 dip switch 3 & 4 setting. When the pumpout timer expires, the pump-out is complete. The pump-out frequency control is factory set for every 10th cycle, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 & 6) can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see "II.C.3.d) PumpOut Frequency Control (S4 dip switch 5 & 6)."

Timing of the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below

S4 Dip Switch Setting

Pump-Out

1st Pump-Out

No. 5

No. 6

Frequency

 

OFF

OFF

Every cycle

After 2nd freeze cycle

 

 

 

 

ON

OFF

Every 2 cycles

After 3rd freeze cycle

 

 

 

 

OFF

ON

Every 5 cycles

After 6th freeze cycle

 

 

 

 

ON

ON

Every 10 cycles

After 11th freeze cycle

51

Page 51
Image 51
Hoshizaki KM-1301SAH/3, KM-1301SRH/3, KM-1301SWH/3 service manual