2. Water-Cooled Condenser
a) Connection to an Open Drain System
•Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" nominal copper water tubing is recommended for the condenser water supply line.
•A condenser water supply line
•Condenser drain outlet is 3/8" FPT. A minimum of 3/8" nominal hard pipe is recommended for the condenser drain line.
•In some areas, a back flow preventer may be required in the cooling water circuit.
•In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze cycle starts. If the condenser drain outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the water‑regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).
Vent Tube
Condenser
Drain Outlet
3/8" FPT
Icemaker
Water Supply
Inlet
1/2" FPT
Condenser Water
Supply Inlet
1/2" FPT
Minimum 3/8"
Nominal Hard
Pipe
Icemaker
Drain Outlet
3/4" FPT
Vent Tube
Fig. 17
| Minimum 3/8" Nominal Copper Water Tubing |
| Minimum 1/2" Nominal Copper Water Tubing |
Icemaker | Icemaker Water Supply Line |
|
| Condenser Water Supply Line |
|
| |
|
| Condenser Water Supply Line |
|
| Drain Valve |
|
| Icemaker Water Supply Line |
|
| Drain Valve |
|
| Minimum 3/4" Nominal Hard Pipe |
|
| Bin Drain Outlet |
|
| See Manufacturer's Instructions |
Bin |
| Separate piping to approved drain. |
|
| Leave a |
|
| gap between the end of each pipe |
|
| and the drain. |
|
| Vent Tube |
| Condensation | |
|
| |
| Drain Outlet |
|
| 3/8" OD Hard Tube |
|
KMH-2000SWH/3
Connection to an Open Drain System
Floor Drain
26