Electrical Features

Fully accessible NEMA 12-style electrical control enclosure

Single-point power and ground connection

Non-fused disconnect switch, lockable

Branch circuit fusing

208-230/3/60 and 460/3/60 volt (consult factory for other voltages)

208-230/1/60 volt on 2 and 3 1/2 hp models

Refrigeration Features

R-22 refrigerant

Hot gas bypass capacity control

High discharge temperature cutout on 2 hp to 30 hp models

High and low refrigerant pressure cutout switches

Fan cycling switch (5 hp to 30 hp air-cooled models only)

High pressure spring actuated relief valve

Multiple refrigeration access ports

Compressor service valves

Hot gas bypass and liquid line shut-off ball valves on 5 hp to 40 hp models

Filter-dryer

Sight glass

Balanced port thermal expansion valve

Controller Features

Off-the-shelf microprocessor-based PID auto-tuning controller with To Process and Set Point LED readout

Microprocessor temperature switch with LCD display for process water freeze protection compressor cutout, and high process water temperature pump cutout

Electronic time delay for proof of water flow/pressure (models w/pump only)

Off-delay water flow timer to prevent short cycling (models w/pump only)

Low refrigerant pressure switch, override timer for low ambient start-up on remote air- cooled and air-cooled chillers with the variable-speed fan option.

Graphic control panel with indicating and warning status lights

Other Features

One year labor warranty and one year compressor warranty

Two year parts warranty

2-40 HP Portable Chillers

Chapter 2: Functional Description

11 of 78