10 hp and 15 hp Remote Air-Cooled Portable Chillers

Nominal operating parameters for remote air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply capacity by 0.83. Nominal 60 Hz capacity flow rate must be maintained.

 

Nominal cooling

Nom.

Com-

 

Refrigeration

 

Power in amps e

 

 

capacity c tons

water

pres-

Nom.

connections

 

460/3/60 f

 

HP

no

1

2

flow

sor

pump

in. dia. ODS

1 pump

2 pumps

 

pump

pump

pump

gpm d

hp

hp

Discharge

Liquid

rated

running

rated

running

10

9.9

9.5

9.4

23.8

10.0

2.0

11/8”

5/8”

22.5

18.2

24.2

 

19.9

15

14.5

14.1

14.0

34.9

15.0

2.0

11/8”

5/8”

29.7

23.9

31.4

 

25.6

cBased on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air. Optional additional process

pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).

dBased on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.

eAn optional oversized process pump adds to the total rated or running chiller amperage. To find the new total chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1

on page 16), and add it to the chiller rated or running amperage.

fMultiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 0.8 for 575/3/60 amperages.

Remote air-cooled portable chillers come standard with mounting rails. Remote air-cooled portable chillers are charged with 25 psi (172.4 kPa/1.72 bars) nitrogen for shipping purposes.

Com-

Process connections, in. NPT

Dimensions

 

Weights

 

pressor

1

2

no pump,

1 pump, no

in inches c

Dry d

Ship. d

Oper. d e

hp

pump

pumps

no tank

tank, to/from

height

width

Depth

lbs.

lbs.

 

lbs.

10.0

1.5”

2.0”

1.5”

1.5” / 2.0”

40.9”

34.0”

74.7”

827

1,052

 

1,159

15.0

2.0”

2.5”

2.0”

2.0” / 3.0”

40.9”

34.0”

74.7”

870

1,095

 

1,202

cTo convert to cm, multiply by 2.54. Add to height dimension based on mounting options.

dWeight is for standard chiller. Some optional features will increase weight.

eOperating weight is with a full 40-gallon (151 liter) reservoir tank of water.