2 hp and 3.5 hp Water-Cooled Portable Chillers

Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83. Nominal 60 Hz capacity flow rate must be maintained.

 

 

 

Nominal

 

 

Condenser water

 

 

 

Nominal cooling

water

Com-

Nominal

Water

flow in gpm

Amp draws g

HP

capacity c in tons

flow

pressor

pump

conn.

Tower

City

460/3/60 h

 

no pump

1 pump

gpm d

hp

hp

in. NPT

water e

water f

rated

running

2

2.1

1.9

5.1

2.0

1.0

1.0”

6.2

4.2

12.2

8.3

3.5

3.6

3.4

8.6

3.5

1.0

1.0”

10.5

7.2

16.4

11.8

cBased on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process pump hp (kW) reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).

dBased on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.

eBased on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum. f Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum.

gAn optional oversized process pump adds to the total rated or running chiller amperage. To find the new total chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 on page 16), and add it to the chiller rated or running amperage.

hMultiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages.

2 hp and 3.5 hp water-cooled portable chillers come standard with 2” (63 mm) swivel casters.

 

 

Process

 

 

 

 

Weights

 

HP

Compressor

connections

Dimensions in inches c

Dry d

Shipping d

Operating d e

 

hp

in. NPT

height

width

depth

lbs.

lbs.

 

lbs.

2

2.0

1.0”

28.3”

22.0”

41.7”

333

363

 

383

3.5

3.5

1.0”

28.3”

22.0”

41.7”

362

392

 

412

cTo convert to cm, multiply by 2.54. Add to height dimension based on mounting options.

dWeight is for standard chiller. Some optional features will increase weight. Multiply by 0.454 to calculate Kg. e Operating weight is with a full 6-gallon (22.7 liter) reservoir tank of water.

2-40 HP Portable Chillers

Chapter 7: Appendix

49 of 78