2-3 Standard Features

Mechanical Features

Compressor. Hermetic scroll compressors are used on 2 hp through 30 hp (1.49 through

23.37kW) models. Semi-hermetic discus compressors are used on the 35 hp and 40 hp (26.20 and 29.83 kW) models.

Evaporator. Stainless steel copper brazed plate evaporators are used on 2 hp through 30 hp models. Shell and tube evaporators are used on the 35 hp and 40 hp models.

Air-Cooled Condenser. Aluminum fin/copper tube with washable filters, package unit only.

Water-Cooled Condenser. 2 hp to 7.5 hp models use tube-in-tube condensers. 10 hp to 40 hp use cleanable shell and tube condensers. All come with cooling water regulating valves for cooling tower water or city water.

Remote Air-Cooled Condenser. 5 hp to 50 hp only. Aluminum fin/copper tube with low ambient control down to –20ºF (-29ºC) via pressure-actuated fan staging and a variable-speed primary fan.

Reservoir. 2 hp and 3 1/2 hp models use a 6 gallon polyethylene tank. 5 hp and 7.5 hp models use a 20 gallon polyethylene tank. 10 hp and 15 hp models use a 40 gallon polyethylene tank. 20 hp to 30 hp models use an 80 gallon polyethylene tank, and 35 hp and 40 hp models use an 80 gallon stainless steel tank.

Piping. Non-ferrous piping for 2 hp through 30 hp models. 35 hp and 40 hp models have ferrous piping.

Pump. Non-overloading ODP motors, horizontally mounted stamped stainless steel or cast bronze construction.

Other Mechanical Features

External fill/drain sight glass

Low process water pressure switch on 2 hp and 3 1/2 hp models

Low process water flow switch on 5 hp to 40 hp models

Galvanized steel mounting rails for remote air-cooled models

NEMA-rated fan motor(s) on air-cooled models

Galvanized structural steel frame, painted cabinetry, with 2 1/2” swivel casters on 2 hp and 3 1/2 hp models. 4” swivel casters on 5 hp to 15 hp models, and 5” swivel casters with brake on 20 hp to 40 hp models.

Valved process water connections

Pressure-actuated process water bypass valve for system protection only; on single pump models only

To process 2 1/2” dual scale liquid-filled water pressure gauge

Fully insulated refrigeration and process water piping

Isolated fan section on air-cooled models, allowing chiller to run during maintenance

20 mesh Y strainer on process water piping into the evaporator

2-40 HP Portable Chillers

Chapter 2: Functional Description

10 of 78

Page 10
Image 10