IMPORTANT: The VESDA filter must be changed regularly to ensure accurate smoke detection readings. For more information about changing the VESDA filters, see the HP Performance Optimized Datacenter 40c G2 Maintenance and Service Guide.

(Optional) Fire suppression system

CAUTION: The POD fire suppression system is manufacturer designed, engineered, and installed to comply with national standards. However, HP does not certify that the installed fire suppression system meets all local jurisdiction requirements. Compliance with local codes is your responsibility, and includes specific local requirements for initial and periodic inspections, certifications, and maintenance.

Any additional local requirements are not covered as part of the option price or basic installation and deployment services, unless specifically included in an executed Statement of Work.

WARNING: Fire suppression agents include a pre-discharge warning and evacuating system. In the event of a fire, all protected space must be evacuated as soon as possible.

IMPORTANT: The fire suppression abort buttons that are located next to each personnel door can be pressed to interrupt the 30-second fire suppression agent release delay for an additional 30 seconds. This button interrupts the countdown, but does not reset the 30-second fire suppression agent release delay. The fire suppression agent release countdown will continue when the abort button is released until the time is exhausted and the fire suppression agent is released.

The fire suppression system contains conventional fire alarm control circuits and includes features required for single or dual-hazard suppression release applications, including a low-toxicity agent. In the event of fire suppression release, the suppression tanks must be refilled by a certified technician.

Fire system operator panel

The panel is configured by the manufacturer in accordance with the local fire marshal and fire code requirements.

The operator panel includes the following:

Alarm status LED

Trouble status LED

Input status LED

Output status LED

Acknowledge button

Alarm Silence button

System Reset button

The fire system and panel are tested by the local certified fire system supplier and witnessed and certified by the local AHJ or fire marshal.

The fire system operator panel requires regular maintenance and service. For more information on the fire system operator panel component, see the Operation and Maintenance Manual for the HP Performance Optimized Datacenter 40c G2.

Life safety systems 20

Page 20
Image 20
HP Performance Optimized Data Center (POD) 40c manual Optional Fire suppression system, Fire system operator panel

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.