Depending on the IT equipment you have installed in your HP POD 40c G2, you can choose to change both default parameters to improve the overall efficiency of your system. To discuss the effects of changing these parameters for your specific HP POD 40c G2, contact HP ("HP contact information" on page 75).

Item

Sensor

Quantity

Description

 

 

 

 

1

Fans

3 banks of 6

Circulates cool air from the heat exchangers

 

 

(18 total) fans

throughout the HP POD 40c G2

 

 

per zone

 

2

Fan power supply assembly

6

Provides power for the fans

Condensation management

CAUTION: To maintain accurate environmental conditions inside the HP POD 40c G2, do not leave the HP POD 40c G2 doors open during operation.

The heat exchanger drip pans collect any condensation that forms on the heat exchangers. The collected condensate drains out of the HP POD 40c G2 through the heat exchanger condensate drains. HP recommends connecting the condensate drains on the HP POD 40c G2 to a facility drain to prevent collection of water near the HP POD 40c G2.

The HP POD 40c G2 has two 3.175 cm (1.25 in) condensate drain outlets, one located at each end of the hot aisle of the HP POD 40c G2 directly connected to the heat exchanger drip pans. The HP POD 40c G2 has two drains for the water main supply and return lines located on the front of the POD.

To avoid excessive buildup of condensate and to conserve energy, raise the cooling water temperature to above the dew point to manage condensation while maintaining the necessary cooling capacity.

Drains

WARNING: Water that drains around the HP POD 40c G2 can cause a potential slip hazard. Use caution where slip hazards are present.

Water from natural condensation will form. Condensation from the heat exchangers flows to the condensation drains at each end of the HP POD 40c G2.