Capacities

HP POD 40c G2 capacity limitations

The capacity limitations for the HP POD 40c G2 are separated into two categories: electrical power and mechanical cooling capacities. Both of these categories are interdependent and must be considered in conjunction with the overall customer requirements.

Electrical and mechanical cooling capacities

Feature

Specification

 

 

Critical IT electrical

2 x 800A feeders at 415Y/240 V, 3-phase, 4-wire,

connections

with equipment ground conductors

 

10.2 x 10.2 cm (4 x 4 in) conduit fittings per feeder

 

provided

 

 

Critical IT power

2N Redundant—576 kW

capacity

 

 

Mechanical cooling

Not applicable

electrical connections

Power for the cooling system fans comes from house

 

power.

 

 

 

Mechanical cooling

N+1 Redundant—400 kW

capacity

Non-redundant—600 kW

 

 

 

Power feeders

IMPORTANT: A licensed electrician must connect the power according to all local and national electrical codes, and must comply with manufacturer specifications.

The HP POD 40c G2 has eight power feeder couplings that provide the entrance for power to the POD. The power feeders route into the top of each electrical panel on the end of the HP POD 40c G2.

Power, electrical, and controls 24