Control cabinet power components
Item | Component | Description |
|
|
|
1 | VESDA power supply and battery | Provides power to the VESDA as well as backup power during a |
| backup | power failure |
2 | Customer connection box | Controls and organizes information monitored by the HP POD |
|
| 40c G2 security components |
|
|
|
3 | ECS modules and relays | Relays for the ECS control, ECS communications, I/O |
|
| connections and terminal block connections |
|
|
|
4 | EPO controller board and house | Connections for the EPO system and fuses for other house panel |
| panel fuses | components |
5 | Dual power supplies with battery | Provides 24 V DC power to the PLC and ECS systems |
| backup |
|
6 | Battery backup power supply | Provides 24 V DC power to the PLC and ECS systems |
Electrical busways
The electrical busway is a modular, overhead electrical distribution system that supplies power to the HP POD 40c G2 IT loads. The HP POD 40c G2 includes eight busways, and each busway can support 200 A.
Power, electrical, and controls 28