To configure the cold aisle low temperature alarm parameters:

1.Select Cold Aisle Low Alarm Temperature. A keypad appears.

2.Enter a temperature alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the cold aisle high temperature alarm parameters:

1.Select Cold Aisle High Alarm Temperature. A keypad appears.

2.Enter a temperature alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the hot aisle temperature alarm parameters

The current temperature parameters appear on the related buttons.

To configure the hot aisle low temperature alarm parameters:

1.Select Hot Aisle Low Alarm Temperature. A keypad appears.

2.Enter a temperature alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the hot aisle high temperature alarm parameters:

1.Select Hot Aisle High Alarm Temperature. A keypad appears.

2.Enter a temperature alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the humidity alarm parameters

The current relative humidity parameters appear on the related buttons.

To configure the low humidity parameters:

1.Select the Humidity Low Alarm. A keypad appears.

2.Enter a humidity alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the high humidity parameters:

1.Select the Humidity High Alarm. A keypad appears.

2.Enter a humidity alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the differential pressure alarm parameters

The current differential pressure parameters appear on the related buttons.

Environmental control system 47