Feature | Specification |
|
|
Facility input temperature to the HP POD | 12ºC to 24ºC (55ºF to 75ºF) |
40c G2 |
|
Working pressure | 1,034 kPa (150 psi) |
HP POD 40c G2 pressure drop | 172.4 kPa (25 psi) |
HP POD 40c G2 water flow rate | 908.5 lpm (240 gpm) |
Chilled water supply and return | • North |
connections | flanges |
| • |
|
|
Each of the six heat exchanger area access hatches are rated NEMA 3R for outdoor use. The exterior of the hatches are coated with a durable finish to protect against corrosion. The access hatches are located on the roof of the POD. The heat exchangers can be accessed from the roof of the POD by removing one of the six access hatches.
Top view shown
Item | Component | Description |
|
|
|
1 | Heat exchangers | Use facility chilled water to cool the air in the HP POD 40c G2 |
2 | Heat exchanger fan | Operate at variable speeds to maintain the preprogrammed differential |
| banks | pressure setpoint and the hot aisle temperature setpoint |
|
|
|
3 | Chilled water supply | Supplies facility chilled water to cool the HP POD 40c G2 |
4 | Chilled water return | Returns heated chilled water to the facility |
Cooling system 58