HP Performance Optimized Data Center (POD) 40c manual Specifications, Electrical specifications

Models: Performance Optimized Data Center (POD) 40c

1 84
Download 84 pages 34.53 Kb
Page 71
Image 71

Specifications

General HP POD 40c G2 specifications

Features

Specifications

 

 

Overall dimensions

Height—3.66 m (12 ft)

 

Length—12.19 m (40 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—16,783 kg (37,000 lb)

 

Maximum fully loaded—46,266 kg (102,000 lb)

Maximum power2

600 kW HP POD 40c G2

Power input voltage

380 VAC to 415 VAC

Power distribution3

8 x 200 A electrical busways

Maximum rack quantity

20 racks

Rack Units (RU) per rack

50 RU

Rack Units (RU) total

1000 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200 VAC to 240 VAC

Minimum quantity of PDUs per HP POD 40c G2

20 (one per rack)

Maximum quantity of PDUs per HP POD 40c G2

40 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass-through-fiber

 

Bulk cable pass-through-copper

 

(Optional) External rated DEMARC box

 

 

1The Empty weight includes the HP POD 40c G2 structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.

2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c G2 is electrically limited to 600 kW.

3The HP POD 40c G2 can be configured for redundancy or non-redundancy.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

8

Frequency

60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380 to 415 V

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 71

Page 71
Image 71
HP Performance Optimized Data Center (POD) 40c manual Specifications, General HP POD 40c G2 specifications