Specifications
General HP POD 40c G2 specifications
Features | Specifications |
|
|
Overall dimensions | • |
| • |
| • |
|
|
Weight1 | |
| Maximum fully |
Maximum power2 | 600 kW HP POD 40c G2 |
Power input voltage | 380 VAC to 415 VAC |
Power distribution3 | 8 x 200 A electrical busways |
Maximum rack quantity | 20 racks |
Rack Units (RU) per rack | 50 RU |
Rack Units (RU) total | 1000 RU |
Average capacity per rack (kW) | 30 kW |
Peak rack capacity | 69 kW |
|
|
Voltage to rack | 200 VAC to 240 VAC |
Minimum quantity of PDUs per HP POD 40c G2 | 20 (one per rack) |
Maximum quantity of PDUs per HP POD 40c G2 | 40 (two per rack) |
Maximum power per PDU | 30A = 17 kW; 60A = 34 kW |
Network supported | Bulk cable |
| Bulk cable |
| (Optional) External rated DEMARC box |
|
|
1The Empty weight includes the HP POD 40c G2 structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.
2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c G2 is electrically limited to 600 kW.
3The HP POD 40c G2 can be configured for redundancy or
Electrical specifications
Electrical busway system information
Feature | Specification |
|
|
Number of busways | 8 |
Frequency | 60 Hz |
Amps (per busway) | 200 A |
Voltage (per busway) | 380 to 415 V |
Grounding | Copper |
Busway configuration |
Specifications 71