The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP POD 40c G2.
Water specifications
The following table describes the chilled water system specifications for the HP POD 40c G2.
Feature | Specification |
|
|
Facility input temperature to the HP POD | 12ºC to 24ºC (55ºF to 75ºF) |
40c G2 |
|
Working pressure | 1,034 kPa (150 psi) |
HP POD 40c G2 pressure drop | 172.4 kPa (25 psi) |
HP POD 40c G2 water flow rate | 908.5 lpm (240 gpm) |
Chilled water supply and return | • North |
connections | flanges |
| • |
|
|
Feature | Specification |
|
|
U height | 50U |
Width | 54.6 cm (21.5 in) |
Depth | 99 cm (39 in)* |
Maximum load weight | 1,360.7 kg (3,000 lb) |
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.
Thermal and air flow performanceMaximum thermal and air flow | HP POD 40c G2 specification |
performance parameters |
|
|
|
Air | Dependent on IT configuration and chilled water inlet temperature |
components) |
|
Chilled water temperature | 12°C to 24°C (55°F to 75°F) |
Total | Variable as required to maintain the hot aisle setpoint temperature |
| and dependent on IT configuration |
|
|
Heat rejection capacity | 600 kW |
Feature | Specification |
|
|
Operating temperature |
Specifications 72