ICP DAS USA 8KE8 #01S3, +2.1234+2.1234 +2.1234 +2.1234 cr, Command, Description, Syntax, Example

Models: 8KE8 8830 8KE4 8430

1 90
Download 90 pages 20.92 Kb
Page 72
Image 72
Command

#AASi

#AASi

 

Command

 

Description

Reads the analog input or counter/frequency module data for all

 

channels from specified slot in the I-8000 unit.

Syntax

#AASi[CHK](cr)

 

 

#

A delimiter character

 

AA

A 2-character HEX module address for the

 

 

specified I-8000 system ,ranging from 01 to FFh

 

Si

The specified slot number. i = 0 to 3 (4 slots) or

 

 

i = 0 to 7 (8 slots)

 

[CHK]

2-characters of checksum

 

(cr)

Character Return(0x0D) for denote the end of

 

 

command

 

Valid Command

>(data)[chk](cr)

 

Invalid Command

?AA[CHK](cr)

 

Syntax error or

communication error may get no response.

 

>

A delimiter for valid command

 

?

A delimiter for invalid command

 

AA

A 2-character HEX module address

 

(data)

A return string from the RTD input module in

 

 

engineering mode.

 

[CHK]

A 2-character checksum

 

(cr)

Carriage Return(0x0D) to denote the end of

 

 

response

Example

Command

#01S3

 

Response

>+2.1234+2.1234 +2.1234 +2.1234 (cr)

 

Description

The data read from analog data input module

 

 

i-87013 (4 channels analog input module) in slot 3

 

 

of the I-8000 system at address 01h is

 

 

+2.1234+2.1234 +2.1234 +2.1234.

Note:

i-87013 Î 4-Channel RTD Analog Input Module

 

i-8017H Î Fast 8-Channel mV/V/mA Analog Input Module

 

i-87017 Î 8-Channel mV/V/mA Analog Input Module

 

i-87018 Î 8-Channel mV/V/mA and Thermocouple Analog Input

 

Module

 

 

i-8080 Î 8-Channel Counter/Frequency Module

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 72