#01S3C1+09.000

#AASiCj

 

 

 

#AASiCj(data)

 

Command

 

Description

Sets the analog voltage output module data from the specified slot and

 

channel in the I-8000 unit. The data format is in engineering units only.

Syntax

#AASiCj(data)[CHK](cr)

 

#

A delimiter character

 

AA

A 2-character HEX module address for the

 

 

specified I-8000 unit ,ranging from 01 to FFh

 

Si

The specified slot number. i = 0 to 3(4 slots) or

 

 

i = 0 to 7(8 slots)

 

Cj

The specified channel number.

 

 

i-87022 Î j = 0 to 1

 

 

i-87024 Î j = 0 to 3

 

 

i-87026 Î j = 0 to 3

 

 

i-8024 Î j = 0 to 3

 

(data)

A decimal value, always engineer unit

 

[CHK]

A 2-character checksum

 

(cr)

Carriage Return (0x0D) to denote the end of

 

 

command

 

Valid Command

> [chk](cr)

 

Invalid Command

?AA[CHK](cr)

 

Any syntax or communication error may receive no response.

 

>

A delimiter for valid command

 

?

A delimiter for invalid command

 

AA

A 2-character HEX module address

 

 

 

 

[CHK]

A 2-character of checksum

 

(cr)

Carriage Return (0x0D) to denote the end of

 

 

response

Example 1:

Command

#01S3C1+09.000

 

Response

> (cr)

 

Description

This example sends the positive value +9.000V to

 

 

the Analog Data output Module in slot 3 and

 

 

channel 1 of the I-8000 unit at address 01h. The

 

 

response indicates the command is valid

Example 2:

Command

#01S3C1-05.000

 

Response

> (cr)

 

Description

This example sends the negative value -5.000V to

 

 

the Analog Data output Module in slot 3 and

 

 

channel 1 of the I-8000 unit at address 01h. The

 

 

response indicates the command is valid

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 74

Page 74
Image 74
ICP DAS USA 8430, 8KE8, 8KE4, 8830 user manual #01S3C1+09.000, #01S3C1-05.000, Command, Description, Syntax, Example