2.2 Creating a virtual COM port to map the I/O modules

2.2 Creating a virtual COM port to map the I/O modules

Step1: Wire the 8430/8830/8KE4/8KE8 and configure its network settings (IP, Mask, Gateway)

Step2: Install the VxComm driver appropriate for your PC (95/98/NT/2000/XP) CD:\Napdos\7188e\tcp\VxComm\Driver(PC)\

Step3: Run the VxComm Utility and connect to the 8430/8830/8KE4/8KE8

Step4: Map the “Port I/O” to a virtual COM port.

Step5: Exit the VxComm Utility

2.3 Configure I/O modules

The DCON Utility is used to configure I-7000, I-8000 and I-87K series I/O modules and communicates with I/O modules via the COM port. For I/O modules on the 8430/8830/8KE4/8KE8, using the VxComm technique can let DCON Utility to access the I/O modules via the Ethernet.

DCON Utility

Main functions Configuring modules

Baudrate

Address Check sum Power on value Safe value… etc. Testing I/O actions

Modules supported: i-7000/i-8000/i-87K series (with DCON protocol)

OS supported:

Windows 98/NT/2000/XP

File location:

CD:\Napdos\Driver\DCON_Utility