ICP DAS USA 8KE4, 8KE8, 8430, 8830 #01S3C0, +2.1234cr, Command, Description, Syntax, Example

Models: 8KE8 8830 8KE4 8430

1 90
Download 90 pages 20.92 Kb
Page 73
Image 73
#01S3C0

#AASiCj

#AASiCj

 

Command

 

Description

Reads the analog input or counter/frequency module data from

 

specified slot and the specified channel in the I-8000 unit.

Syntax

#AASiCj[CHK](cr)

 

 

#

A delimiter character

 

AA

A 2-character HEX module address for the

 

 

specified I-8000 unit, ranging from 01 to FFh

 

Si

The specified slot number. i = 0 to 3 (4 slots) or

 

 

i = 0 to 7 (8 slots)

 

Cj

specified channel number.

 

 

i-87013 Î j = 0 to 3

 

 

i-8017H Î j = 0 to 7

 

 

i-87017 Î j = 0 to 7

 

 

i-87018 Î j = 0 to 7

 

 

i-8080 Î j = 0 to 7

 

[CHK]

The 2-character of Checksum

 

(cr)

Carriage Return(0x0D) for denote the end of the

 

 

command

 

Valid Command

>(data)[chk](cr)

 

Invalid Command

?AA[CHK](cr)

 

Any syntax or communication error may receive no response.

 

>

A delimiter for valid command

 

?

A delimiter for invalid command

 

AA

A 2-character HEX module address

 

(data)

A return string from RTD input module in

 

 

engineering mode.

 

[CHK]

A 2-character checksum

 

(cr)

Carriage Return (0x0D) to denote the end of the

 

 

response

Example

Command

#01S3C0

 

Response

>+2.1234(cr)

 

Description

The data read from the analog data input module

 

 

in slot 3 and channel 0 of the I-8000 unit at address

 

 

01h is +2.1234.

Notes:

i-87013 Î 4-Channel RTD Analog Input Module

 

i-8017H Î Fast 8-Channel mV/V/mA Analog Input Module

 

i-87017 Î 8-Channel mV/V/mA Analog Input Module

 

i-87018 Î 8-Channel mV/V/mA and Thermocouple Analog Input

 

Module

 

 

i-8080 Î 8-Channel Counter/Frequency Module

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 73

Page 73
Image 73
ICP DAS USA 8KE4, 8KE8, 8430, 8830 user manual #01S3C0, +2.1234cr, Command, Description, Syntax, Example