The differences between I-8000 and I-87K series I/O modules are

Item

i-8000 series

i-87K series

Microprocessor

No

Yes (8051)

Communication interface

Parallel bus (Note1)

Serial bus (Note2)

Communication speed

Fast

Slow

DI latched function

No

Yes

Counter input (for digital input module)

No

Yes (100 Hz)

Power on value

Yes (Note3)

Yes

Safe value

Yes (Note3)

Yes

Host watchdog

Yes

Yes

Module watchdog

No

Yes

Programmable slew-rate for AO module

No

Yes

Note:

1.The 8000 series and 87K I/O modules can both be connected into the same i-8000 MCU, for there are two types of buses on i-8000 series main-board. Through the parallel bus, the CPU can communicate with I/O modules very fast. For digital I/O modules, the communication time takes less than 0.012 ms. For analog I/O modules, it depends on the modules. For example, I-8017H’s scan rate is 50K samples per second and I-8024’s throughput is 2100 samples per second.

2.Through the serial bus (RS-485), the communication speed is 115200 bps Maximum. The communication time depends on the command and response length (bytes). Normally, for digital I/O modules, one module takes less then 1 ms; for analog I/O modules, one sample takes less than 2 ms.

3.The hardware design of the I-8000 series I/O modules doesn’t have the power on value and safe value. Running the DCON firmware on the I-8000 MCU, they can have the functions.

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 84

Page 84
Image 84
ICP DAS USA 8KE8, 8KE4, 8430, 8830 user manual i-8000 series, i-87K series