#01S31C01

# AASiBjDS For single channel DO output

Command

#AASiBjDs

 

 

Description

This command sends the value to the digital output module of the specified

 

channel and slot of the I-8000 unit. This command is only for output

 

modules which the channel number is less than or equal to 16.

 

Syntax

#AASi1BDs[CHK](cr)

 

 

$

A delimiter character

 

 

AA

A 2-character HEX module address for the specified

 

 

I-8000 unit ,ranging from 01 to FFh

 

 

Si

The specified slot number. i = 0 to 3(4 slots) or

 

 

i = 0 to 7(8 slots)

 

 

Bj

The channel to be set will contain two characters.The

 

 

first character ‘B’ is always be number 1, and the

 

 

second character ‘j’ indicates the channel will be set

 

 

and ranging from 0 to F.

 

 

Ds

For single channel output the data will contain two

 

 

character. The first character ‘D’ is always 0. The

 

 

second character is ether 0 or 1. 0 => OFF, 1 => ON.

 

[CHK]

2-characters of Checksum

 

 

(cr)

Carriage Return (0x0D) to denote the end of

the

 

 

command

 

 

Valid Command

>[chk](cr)

 

 

Invalid Command

?AA[CHK](cr)

 

 

Any syntax or communication error may receive no response.

 

 

>

A delimiter for valid command

 

 

?

A delimiter for invalid command

 

 

[CHK]

A 2-character of checksum

 

 

 

 

 

 

(cr)

Carriage Return (0x0D) to denote the end of

the

 

 

response

 

Note

If any channel of

digital output module (*1) is configured for an analog

 

input alarms then this command has no effect on the specified channel.

 

The channel is always used for analog input alarms and can not be

 

configured again unless it is disconnected.

 

 

Refer to: Analog Input Alarm

 

 

(*1) For digital output modules not support analog input alarm are :

 

 

i-8041, i-87041, i-87042, i-8050

 

Example

Command

#01S31C01

 

 

Response

>(cr)

 

 

Description

This example is for a single channel. The Digital

 

 

output Module in slot 3 and channel 12 (0Ch) of the

 

 

I-8000 unit at address 01h will be set to ON. This

 

 

example is only for output modules which the channel

 

 

number is less than or equal to 16.

 

 

Command

#01S31A00(cr)

 

 

Response

>(cr)

 

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 78