ACCESSORY CONNECTIONS
The furnace control will allow
ELECTRONIC AIR CLEANER CONNECTION
Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during circulating blower operation.
HUMIDIFIER CONNECTION
Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.
A mounting hole is provided on the control panel next to the furnace control board for mounting a humidifier transformer if required.
TWINNING
These furnaces are not to be twinned. If more than one furnace is needed in an application, each furnace must have its own complete duct system and its own wall thermostat.
SECTION VI: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION
CONDENSATE DRAIN LOCATION
As shipped from the factory:
•For all 060, & 080K input furnaces the main drain is plumbed through the casing
•For all 100 & 120K input furnaces the main drain is plumbed through the casing
NOTE: The Figures 24 - 27 show the condensate drain arrange- ment for the various possible furnace and vent blower positions.
The condensate hoses must slope downwards at all points.
The furnace condensate pan is self priming and con- tains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.
When drain hose routing changes are required (shown in Figures 24- 27), be sure to cap all
If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.
No hose clamps are needed for connecting to the condensate pan.
The furnace, evaporator coil, and humidifier drains may be com- bined and drained together. The evaporator coil drain must have an external,
Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4" per foot (21 mm/m) downward slope to the drain.
If an external vent tee is being installed, then it must have its own condensate trap before it is disposed into an open or vented drain.
This is not to be considered as a second trap as referenced elsewhere in this document.
Open Stand Pipe
5” Min.
Tee
To Open Or
Vented Drain
FIGURE 22: Typical. Condensate drain, vertical installation.
The condensate will flow to the drain better if an open stand pipe is installed in the drain line. See Figure 23.
If evaporator coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher, above the 5” minimum.
It is possible for condensation to form inside the combustion air (intake) pipe in the summer months if significant length of combus- tion air pipe passes through conditioned space. This problem can be averted by the addition of a simple drain tee, or a drain tee with a drain on the combustion air pipe as close to the furnace as possi- ble, as shown in Figure 24. This is true for all long horizontal vent- ing in any furnace configuration. This will prevent the condensate from entering the furnace.
16 | Johnson Controls Unitary Products |