438335-UIM-B-0509

Table 7: Ratings & Physical / Electrical Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Output

Nominal

Cabinet Width

Total Unit

AFUE

High Fire

Low Fire

High/Low

High/Low

Airflow

Air Temp. Rise

Air Temp. Rise

 

 

Amps

 

MBH

kW

MBH

kW

CFM

m3/min

in.

cm

%

°F

°C

°F

°C

 

60/39

18/11

58/37

17/11

1200

34

17-1/2

44.4

9

96

35 - 65

1.6 - 18.3

35 - 65

1.6 - 18.3

80/52

23/15

77/50

22/14

1200

34

17-1/2

44.4

9

96

35 - 65

1.6 - 18.3

30 - 60

-1 - 15.5

80/52

23/15

77/50

22/14

1600

45.3

21

53.3

12

96

35 - 65

1.6 - 18.3

35 - 65

1.6 - 18.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100/65

29/19

96/62

28/18

1600

45.3

21

53.3

12

96

35 - 65

1.6 - 18.3

30 - 60

-1 - 15.5

100/65

29/19

96/62

28/18

2000

56.6

21

53.3

14

96

35 - 65

1.6 - 18.3

35 - 65

1.6 - 18.3

120/78

35/23

115/75

33/22

2000

56.6

24-1/2

62.2

14

96

35 - 65

1.6 - 18.3

35 - 65

1.6 - 18.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Max. Outlet

Blower

Blower Size

Max.

Min. Wire Size

Operating

 

 

High/Low

Air Temp.

Over-current

(awg) @ 75 ft.

Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protect

One Way

 

 

 

 

MBH

kW

°F

°C

HP

Amps

in.

cm

Lbs.

Kg.

 

 

60/39

18/11

170

76.7

1/2

7

11 x 8

27.9 x 20.3

15

14

122

55.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80/52

23/15

175

79.4

1/2

7

11 x 8

27.9 x 20.3

15

14

126

57.1

 

 

80/52

23/15

175

79.4

3/4

10.2

11 x 10

27.9 x 25.4

15

14

136

61.7

 

 

100/65

23/15

175

79.4

3/4

10.2

11 x 10

27.9 x 25.4

15

14

142

64.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100/65

29/19

175

79.4

1

12.7

11 x 11

27.9 x 27.9

20

12

145

65.7

 

 

120/78

35/23

170

76.7

1

12.7

11 x 11

27.9 x 27.9

20

12

156

70.7

 

 

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE test procedures.

Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water.

SUPPLY VOLTAGE CONNECTIONS

Junction

Box

Connect ground lead to screw

Electrical Entry

L1-Hot BLK

Neutral WHT

FIGURE 17: Electrical Wiring

1.Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/national electrical codes. The switch should be close to the unit for conve- nience in servicing. With the disconnect or fused switch in the OFF position, check all wiring against the unit wiring label. Refer to the wiring diagram in this instruction.

2.Remove the wiring box cover screws. Route all power wiring through a conduit connector or other proper bushing that has been installed into the unit opening and the junction box. In the junction box there is a black wire, a white wire and a green ground screw. Connect the power supply as shown on the unit’s wiring label located on the inside of the blower compartment door, or the wiring schematic in this section. Connect the black wire to L1 (hot) from the power supply. Connect the white wire to neutral. Connect the ground wire (installer-supplied) to the green (equipment ground) screw. An alternate wiring method is to use a field-provided 2”

(5.1 cm) x 4” (10.2 cm) box and cover on the outside of the fur- nace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring connections replace the wiring box cover and screws. Refer to Figures 17.

3.The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figures 17.

The power connection leads and wiring box may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes provided.

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that come with the thermostat. With the thermostat set in the OFF position and the main electrical source disconnected, connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module, as shown in Figures 18. Electronic ther- mostats may require the common wire to be connected. Apply strain relief to thermostat wires passing through cabinet. If air conditioning equipment is installed, use thermostat wiring to connect the Y and C terminals on the furnace control board to the proper wires on the con- densing unit (unit outside).

Set the heat anticipator in the room thermostat to 0.4 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa- tors. They should be set to six cycles per hour. Follow the thermo- stat manufacturer's instructions.

The 24-volt, 40 VA transformer is sized for the furnace components only, and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.

Johnson Controls Unitary Products

11

Page 11
Image 11
Johnson Controls TM9V MP installation manual Supply Voltage Connections, LOW Voltage Control Wiring Connections, Afue, Lbs

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.