ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 7 “ELECTRICAL AND PERFORMANCE DATA”.
The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the fur- nace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause premature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.
After about 5 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.83 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
VARIABLE SPEED MOTORS
The variable speed motor must be configured so the blower will provide a sufficient airflow so that the furnace operates with in the temperature rise range on the rating plate and within the application limitations shown in Table 7 in these Instructions.
ADJUSTMENT OF FAN CONTROL SETTINGS
Heating Indoor Fan Off Delay
This furnace is equipped with a
BLOWER OFF | HI HEAT DELAY | CONTINUOUS FAN |
DELAY JUMPER | JUMPER | SPEED JUMPER |
LOW VOLTAGE |
TERMINALS |
BLOWER SPEED |
JUMPERS |
HEAT |
DELAY |
JUMPER |
DEHUMIDISTAT JUMPER | COOLING PROFILE JUMPER |
FIGURE 41: Furnace Control Board
SECTION IX: SAFETY CONTROLS
CONTROL CIRCUIT FUSE
A
BLOWER DOOR SAFETY SWITCH
Main power to the unit must still be interrupted at the main power disconnect switch before any service or repair work is to be done to the unit. Do not rely upon the interlock switch as a main power dis- connect.
Blower and burner must never be operated without the blower panel in place.
This unit is equipped with an electrical interlock switch mounted in the burner compartment. This switch interrupts all power at the unit when the panel covering the blower compartment is removed.
Electrical supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned.
ROLLOUT SWITCH CONTROLS
These controls are mounted on the burner assembly. If the temperature in the area surrounding burner exceeds its set point, the gas valve is
PRESSURE SWITCHES
This furnace is supplied with three pressure switches, which monitor the flow through the combustion air/vent piping and condensate drain sys- tem. These switches
1.Blockage of vent piping or terminal.
2.Failure of combustion air blower motor.
3.Blockage of combustion air piping or terminals.
4.Blockage of condensate drain piping.
32 | Johnson Controls Unitary Products |