RI.

HI.

Type

R/W

Tag

Description

88

58

2 Bytes

CNF

 

AIT1

Input Type of Analog Input 1

 

 

0 0 0 0

0 X11

X10

X9

Unit of Measure

 

 

X8 X7 X6 X5 X4 X3

X2

X1

 

 

 

X4 X3 X2 X1

 

 

 

 

 

 

= 0000

 

 

 

No Units

 

 

= 0001

 

 

 

Degrees Celsius or Kelvin

 

 

= 0010

 

 

 

Degrees Fahrenheit

 

 

= 0011

 

 

 

Percent

 

 

X5 = 1

 

 

 

Enable Square Root of Input

 

 

X6 = 1

 

 

 

Alarm on Unfiltered Value

 

 

X7 = 0

 

 

 

0-10 Volts

 

 

X7 = 1

 

 

 

0-2 Volts, 0-20 mA or RTD

 

 

X8 = 1

 

 

 

20 % Suppression

 

 

X11 X10 X9

 

 

Linearization and Sensor Type

 

 

= 000

 

 

 

Linear (active sensor)

 

 

= 001

 

 

 

Nickel 1000 (JCI)

 

 

= 010

 

 

 

Nickel 1000 Ext. Rng

 

 

= 011

 

 

 

A99 Sensor

 

 

= 100

 

 

 

PT1000 Sensor

89

59

Number

CNF

 

HR1

High Range Analog Input 1

90

5A

Number

CNF

 

LR1

Low Range Analog Input 1

91

5B

Number

R/W (E)

 

HIA1

High Alarm Limit Analog Input 1

92

5C

Number

R/W (E)

 

LOA1

Low Alarm Limit Analog Input

93

5D

Number

R/W (E)

 

ADF1

Differential on Alarm Limit [units]

94

5E

Number

CNF

 

FTC1

Filter Constant Analog Input 1

95

5F

2 Bytes

 

 

 

Spare

96

60

2 Bytes

CNF

 

AIT2

Input Type of Analog Input 2 (bits

 

 

 

 

 

 

as AIT1)

97

61

Number

CNF

 

HR2

High Range Analog Input 2

98

62

Number

CNF

 

LR2

Low Range Analog Input 2

99

63

Number

R/W (E)

 

HIA2

High Alarm Limit Analog Input 2

100

64

Number

R/W (E)

 

LOA2

Low Alarm Limit Analog Input 2

101

65

Number

R/W (E)

 

ADF2

Differential on Alarm Limit [units]

102

66

Number

CNF

 

FTC2

Filter Constant Analog Input 2

103

67

2 Bytes

 

 

 

Spare

Configuration Guides—XT-9100 Configuration Guide 35

Page 35
Image 35
Johnson Controls XT-9100 CNF AIT1, CNF HR1, CNF LR1, HIA1, LOA1, ADF1, CNF FTC1, CNF AIT2, CNF HR2, CNF LR2, HIA2, LOA2