Johnson Controls XP-910x, XT-9100 appendix Analog Input

Models: XT-9100 XP-910x

1 40
Download 40 pages 55.15 Kb
Page 10
Image 10
Analog Input

Analog Input

Configuration

AI Input Type:

Measurement

Units

Note: The data base in the XT-9100 has been designed to accept most configuration of inputs and outputs. All inputs and outputs which are physically connected through expansion modules must be configured, and only those points. If there is a difference between the physical configuration and the software configuration, the XT-9100 will signal an error condition to the DX-9100 (XTnERR).

Each analog input is defined and configured by the following parameters:

Tag name (optional, GX-only)

Measurement units (for RTD inputs)

Enable square root

Alarm on unfiltered value

Input signal range

Alarm limits

Filter time constant

The GX Tool determines the input signal range with a 2-stage process: you must first decide if the input is active or passive; the remaining options depend on this choice. With the SX Tool, this information is entered into a number of Items.

Via the GX Tool

Select XTn, AIn, then either Active or Passive.

Note: All AI points must be configured even if not connected to a sensor to enable the generation of a complete IO Map and to ensure correct operation with the DX-9100 Controller.

Via the GX Tool

The selection of Celsius or Fahrenheit, is set in the Global data of the DX-9100 (select DX-9100, then Global. At the “Temperature Units” field, enter “C” for Celsius or “F” for Fahrenheit).

To determine the measurement units of active inputs, select XTn, AIn, Data, and then enter in the “Measurement Units” field:

0 = None

1 = Temperature (“C” or “F” as entered in Global)

2 = Percent (%)

Note: The units of an active input are not read by the DX-9100 Controller, but are available to any other Supervisory System which may be connected.

10Configuration Guides—XT-9100 Configuration Guide

Page 10
Image 10
Johnson Controls XP-910x, XT-9100 appendix Analog Input