Johnson Controls XP-910x, XT-9100 appendix Hardware Configuration Model Codes, XT/XP/TR Model Codes

Models: XT-9100 XP-910x

1 40
Download 40 pages 55.15 Kb
Page 4
Image 4
Hardware Configuration

Hardware Configuration

Model Codes

For full details of the hardware configuration, refer to the XT-9100 Technical Bulletin (LIT-6364040).

An XT-9100 combined with expansion modules provides the following configurations, either:

eight analog inputs/outputs, or

eight digital inputs/outputs, with digital counters associated with the digital inputs, or

eight analog inputs/outputs and eight digital inputs/outputs, or

sixteen digital inputs/outputs, with digital counters associated with the digital inputs within the first eight inputs/output points

The extension module address is set with the address switches on the XT-9100. When connected to a DX-9100 controller, this address must also be set in the DX-9100 software configuration. The address must be unique not only on the XT-Bus, but also on the N2 Bus (Bus 91) to which the DX-9100 is connected.

The XT-9100 must be supplied with a 24 VAC power source. All models are suitable for 50 Hz or 60 Hz through software configuration.

For the analog inputs and outputs, the input and output type are set by jumpers on the analog expansion module board. These settings must comply with the software configuration settings.

Note: When an extension module is configured with 16 inputs/outputs, the DX-9100 considers the single physical module as two logical modules, each with eight inputs/outputs. A DX-9100 can communicate with up to eight logical modules, with a maximum of 64 inputs/outputs.

Table 1: XT/XP/TR Model Codes

XT-9100-8004

Extension Module

24 VAC supply

XP-9102-8004

Expansion Module

6 analog inputs

 

 

2 analog outputs

XP-9103-8004

Expansion Module

8 digital outputs (triacs)

XP-9104-8004

Expansion Module

4 digital inputs

 

 

4 digital outputs (triacs)

XP-9105-8004

Expansion Module

8 digital inputs

XP-9106-8004

Expansion Module

4 digital outputs (relay)

TR-9100-8001*

Transformer, 24V/12 VA

Primary: 240 VAC

TR-9100-8002*

Transformer, 24V/12 VA

Primary: 220 VAC

* TR-9100 is not available in North America.

4Configuration Guides—XT-9100 Configuration Guide

Page 4