GF 100 DV II Nordic QT GF 200 DV II Lillehammer

Horizontal Vent Termination

„Wall Cut-out Opening: A minimum 10" X 10"

(250 mm x 250 mm) square hole is required for proper pipe clearances through a combustible wall. Use one of the approved vent manufacturers’ WALL THIMBLE for the wall penetration.

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.

„The minimum horizontal run made directly off the rear of the stove into a standard horizontal cap shall be no less than a 6” (152 mm) vent section. See fig. 11.

„The maximum horizontal run made directly off the rear of the stove into a standard horizontal termina- tion must not exceed 4 ft. (1219 mm) See fig. 11.

„Corner Installation: Max. Horizontal Run is 2 ft. (610 mm). See Fig. 12.

„A horizontal termination must fall within the shaded area illustrated in fig. 7, Vent Termination Diagram.

„The horizontal termination cap must maintain a 3" clearance to any overhead combustible projections 2 1/2" or less. It must also maintain 12" clearance from projections exceeding 2 1/2". See fig. 14.

„Any horizontal run of vent must be level or have a 1/4" rise for every foot of run toward the termination cap. NEVER ALLOW THE VENTING TO RUN DOWN-

WARD FROM STOVE TO TERMINATION; DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERA- TURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE.

„Install a Vinyl Siding Standoff between the vent termination and an exterior wall covered by vinyl siding material to prevent potential heat damage to the siding.

„Do not recess the termination cap into a wall or siding.

Zero

Decorative

Wall Shield

Clearance

 

to Rear

Min. 6 in.

 

Max. 48 in.

 

Horizontal Run

 

Standard

 

Horizontal

 

Termination

Figure 11. Min. / Max. Horizontal Run

 

Min. 6”

(152 mm)

45°

Max. 24”

(610 mm)

Elbow

 

 

 

 

See Note F

 

 

Fig. 17

Min. 2”

 

 

51 mm

 

 

Standard

Horizontal

Termination

Cap

Wall Thimble

and Trim Collar

Min. 2” 51 mm

Figure 12. Corner Installation, Horizontal Termination directly off rear. Maximum Horizontal run is 2 ft.

(610 mm).

12

Page 12
Image 12
Jotul GF 100 DV II, GF 200 DV II manual Horizontal Vent Termination, Min. / Max. Horizontal Run