Masonry or Prefabricated Chimney Conversion
The GF 400 DV Sebago is approved for use with listed chimney conversion kits from any of the manufacturers listed on page 8. These kits are for use in a masonry chimney or a prefabricated solid fuel listed chimney. See
| Exhaust | Vertical |
| Termination | |
| Gas | |
| Cap | |
|
| |
Cap Adaptor- |
|
|
included in |
| Intake Air |
#934 Kit |
| |
|
|
fig. 15.
These installation requirements must be followed:
1.Use the guidelines for Coaxial Vent Termination appropriate for your gas type on pages 11 - 12.
2.In masonry chimney, a fireclay liner or listed steel liner, must be present the entire length of the chim- ney.
3.Chimney height should not exceed 35 ft. (10.66 m).
4.The liner must have an inside dimension of 6” round or greater.
5.Prefabricated chimneys must be UL 103 or ULC
4” Flex Pipe not included in kit
Support/Wall Thimble Cover
Use standard vent pipe from stove to thimble from the same manufacturer
IMPORTANT NOTICE
THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI
SULTING ITS/WHI PRODUCT CERTIFI- CATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD.
Figure 15. Vent System through a masonry chimney using a chimney conversion kit. May also be used in listed prefabricated chimneys. Drawing is for illustrative purposes only - DO NOT VENT TWO APPLIANCES INTO A SINGLE CHIMNEY.
13