Horizontal Termination

Horizontal Termination

„Any horizontal termination must fall within the shaded portion of the vent window graph illustrated in figs. 9 or 11. For Snorkel Terminations, see below.

„Any horizontal termination except a snorkel termination, must include:

1)Minimum rise of 2 ft.

2)Minimum horizontal run of 12 in. when vertical run is less than 8 ft.

2)Maximum rise of 35 ft.

3)Maximum horizontal run of 27 ft.

4)No more than four 45° or two 90° Elbows

„Follow all termination clearance guidelines as speci- fied in fig. 19.

„The horizontal termination cap must maintain a 3" clearance to any overhead combustible projections 2 1/2" or less. It must also maintain 12" clearance from projections exceeding 2 1/2". See fig. 20.

„Wall Cut-out Opening: A minimum 10" X 10" (250 mm x 250 mm) square hole is required for proper pipe clear- ances through a combustible wall. Use a listed wall thimble for the wall penetration.

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.

„Any horizontal run of vent must have a 1/4" rise for every foot of run toward the termination cap. NEVER ALLOW THE VENTING TO RUN DOWNWARD FROM STOVE TO TERMINATION; DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE.

„Install a Vinyl Siding Standoff between the vent termination and an exterior wall covered by vinyl siding material to prevent potential heat damage to the siding.

„Do not recess the termination cap into a wall or siding.

Snorkel Terminations

„THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN FOR ANY SNORKEL TERMINATION. See Fig. 6, pg. 9.

„With a 14” Snorkel:

The horizontal run made directly off the rear of the stove into a 14” snorkel cap should include no more than a single 12” straight section as shown in fig. 17. One 45° Elbow may be used for a corner installation as shown in fig. 18.

„With a 36” Snorkel:

The maximum horizontal run may be no more than 6 ft. (182 cm.)

Snorkel Terminations 12 in. (305 mm)

C

L

24 in.

 

Snorkel

 

(305 mm)

 

14”

 

355 mm

57”

Max.

(1448 mm)

 

12”

25

1/2

in.

Vent

Snorkel

Pipe or

(648 mm)

less

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 16.

Minimum vent for horizontal termination.

14” Maximum horizontal run directly off rear of stove with 14” Snorkel termination.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

in.

 

 

Max.

 

 

Snorkel

6 ft.

 

(915 mm)

183 cm

Figure 17. Maximum Horizontal and Vertical Run with 36” Snorkel Termination.

 

Max.

45° Elbow

14”

355 mm

 

 

See Note F

 

Fig. 20

12 in. Straight Pipe

Wall Thimble

and Trim Collar

Figure 18. Corner Installation with 14” Snorkel Termination.

14