Proper Combustion

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com­ bustion. Take combustion sample beyond the flue outlet and compare to the tables below.

TABLE 12

ML193

CO2% For Nat

CO2% For L.P.

Unit

 

 

 

 

 

-045

 

 

 

 

 

-070

 

 

 

 

 

-090

7.2 - 7.9

8.6 - 9.3

 

 

 

-110

 

 

 

 

 

-135

 

 

 

 

 

The maximum carbon monoxide reading should not exceed 50 ppm.

High Altitude Information

NOTE - In Canada, certification for installations at eleva­ tions over 4500 feet (1372 m) is the jurisdiction of local au­ thorities.

ML193UH units require no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048 m) above sea level. Units installed at altitude of 4501 - 10,000 feet (1373 to 3048m) require a pressure switch change which can be ordered separately. Table 13 lists conversion kit and pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory-set and re­ quires no adjustment.

NOTE - A natural to LP/propane gas changeover kit is nec­ essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

TABLE 13

Conversion Kit and Pressure Switch Requirements at Varying Altitudes

 

Natural to

High Altitude

LP/Propane

High Altitude

 

 

 

Natural Burner

to

LP/Propane

High Altitude Pressure Switch

ML193

LP/Propane

Orifice Kit

Natural

Burner Orifice Kit

 

 

 

 

 

Unit

 

 

 

 

 

 

0 - 7500 ft

7501 - 10,000 ft

0 - 7500 ft

7501 - 10,000 ft

4501 - 7500 ft

7501 -10,000 ft

 

 

(0 - 2286m)

(2286 - 3038m)

(0 - 2286m)

(2286 - 3038m)

(1373 - 2286m)

(2286 - 3048m)

 

 

 

 

 

 

 

-045

 

 

 

 

 

 

 

 

 

 

 

 

 

-070

 

 

 

 

 

 

 

 

 

 

 

 

 

-090

*69W73

73W37

*73W81

*68W68

93W87

93W88

 

 

 

 

 

 

 

-110

 

 

 

 

 

 

 

 

 

 

 

 

 

-135

 

 

 

 

 

 

 

 

 

 

 

 

 

* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.

Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).