Lennox International Inc ML193UH Attic or Crawl Space For Intake Air in Feet, Number Of, 2” Pipe

Models: Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge ML193UH

1 51
Download 51 pages 42.64 Kb
Page 18
Image 18
Standard Termination at Elevation 0 - 10,000

TABLE 5

Maximum Allowable Intake or Exhaust Vent Length in Feet

NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.

NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.

Standard Termination at Elevation 0 - 10,000

Number Of

 

 

2” Pipe

 

 

 

 

 

2-1/2” Pipe

 

 

 

 

 

3” Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Elbows

 

 

Model

 

 

 

 

 

 

Model

 

 

 

 

 

Model

 

 

Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

045

070

090

110

 

135

045

070

 

090

 

110

 

135

045

070

090

110

135

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

81

66

44

24

 

 

115

100

 

68

 

43

 

 

137

137

118

118

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

76

61

39

19

 

 

110

95

 

63

 

38

 

 

132

132

113

113

109

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

71

56

34

14

 

 

105

90

 

58

 

33

 

 

127

127

108

108

104

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

66

51

29

 

 

 

100

85

 

53

 

28

 

 

122

122

103

103

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

61

46

24

 

 

n/a

95

80

 

48

 

23

 

n/a

117

117

98

98

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

56

41

19

 

 

90

75

 

43

 

18

 

112

112

93

93

89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

51

36

14

n/a

 

 

85

70

 

38

 

13

 

 

107

107

88

88

84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

46

31

 

 

 

 

80

65

 

33

 

 

 

 

102

102

83

83

79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

41

26

n/a

 

 

 

75

60

 

28

 

n/a

 

 

97

97

78

78

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

36

21

 

 

 

 

70

55

 

23

 

 

 

 

92

92

73

73

69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Concentric Termination Elevation 0 - 10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number Of

 

 

2” Pipe

 

 

 

 

 

2-1/2” Pipe

 

 

 

 

 

3” Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Elbows

 

 

Model

 

 

 

 

 

 

Model

 

 

 

 

 

Model

 

 

Usedl

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

045

070

090

110

 

135

045

070

 

090

 

110

 

135

045

070

090

110

135

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

73

58

42

22

 

 

105

90

 

64

 

39

 

 

121

121

114

114

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

68

53

37

17

 

 

100

85

 

59

 

34

 

 

116

116

109

109

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

63

48

32

12

 

 

95

80

 

54

 

29

 

 

111

111

104

104

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

58

43

27

 

 

 

90

75

 

49

 

24

 

 

106

106

99

99

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

53

38

22

 

 

n/a

85

70

 

44

 

19

 

n/a

101

101

94

94

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

48

33

17

 

 

80

65

 

39

 

14

 

96

96

89

89

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

43

28

12

n/a

 

 

75

60

 

34

 

 

 

 

91

91

84

84

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

38

23

 

 

 

 

70

55

 

29

 

n/a

 

 

86

86

79

79

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

33

18

n/a

 

 

 

65

50

 

24

 

 

81

81

74

74

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

28

13

 

 

 

 

60

45

 

19

 

 

 

 

76

76

69

69

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 6

Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated

Attic or Crawl Space For Intake Air in Feet

NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.

Standard Termination at Elevation 0 - 10,000

Number Of

 

 

2” Pipe

 

 

 

 

2-1/2” Pipe

 

 

 

 

3” Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Elbows

 

 

Model

 

 

 

 

 

Model

 

 

 

 

Model

 

 

Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

045

070

090

110

135

045

070

 

090

 

110

135

045

070

090

110

135

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

71

56

34

14

 

100

95

 

53

 

28

 

117

117

98

98

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

66

51

29

9

 

95

80

 

48

 

23

 

112

112

93

93

89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

61

46

24

4

 

90

75

 

43

 

18

 

107

107

88

88

84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

56

41

19

 

 

85

70

 

38

 

13

 

102

102

83

83

79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

51

36

14

 

n/a

80

65

 

33

 

8

n/a

97

97

78

78

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

46

31

9

n/a

 

75

60

 

28

 

3

 

92

92

73

73

69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

41

26

4

 

70

55

 

23

 

 

 

87

87

68

68

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

36

21

n/a

 

 

65

60

 

18

 

n/a

 

82

82

63

63

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

31

16

 

 

60

45

 

13

 

 

 

77

77

58

58

54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 18

Page 18
Image 18
Lennox International Inc ML193UH Attic or Crawl Space For Intake Air in Feet, Standard Termination at Elevation 0 - 10,000