ML193UH with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal
Evaporator
Coil
4”min |
5”max |
5’ max.
PVC Pipe Only
Field Provided Vent
(4” min. to 5” max. above condensate connection)
|
| Condensate |
|
|
| Drain Connection |
|
Drain Pan | (Trap at coil is optional) | *Piping from furnace and evaporator coil must |
|
|
| slope down a minimum 1/4” per ft. toward trap |
|
|
| FIGURE 51 | . |
|
|
|
ML193UH with Evaporator
Coil Using a Common Drain
Evaporator drain
line required
(Trap at coil is optional)
(1” min. to 2” Max.above condensate drain connection)
Condensate
DrainConnection
IMPORTAN
T
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in or der for the furnace pressure switch to operate properly.
FIGURE 52
ML193UH with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Evaporator
Coil
(Trap at coil is optional)
Drain Pan
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
Drain Connection
*Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
(4” min. to 5” Max.above condensate drain connection)
FIGURE 53
Page 32