Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge, ML193UH

Models: Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge ML193UH

1 51
Download 51 pages 42.64 Kb
Page 37
Image 37
Electrical

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

ELECTROSTATIC DISCHARGE (ESD)CAUTION

Electrostatic discharge can affect elec­ tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.

INTERIOR MAKE-UP BOX INSTALLATION

remove and relocate

plug to unused

opening on left side

MAKE-UP

BOX

Right Side

FIGURE 59

The unit is equipped with a field make-up box. The make- up box may be moved to the right side of the furnace to fa­ cilitate installation. Seal unused openings on left side with plugs removed from right side. Secure the excess wire to the existing harness to protect it from damage.

Refer to figure 60 for schematic wiring diagram and trou­ bleshooting.

The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.

NOTE - Unit nameplate states maximum current draw. Maximum Over-Current Protection allowed is 15 AMP.

Holes are on both sides of the furnace cabinet to facilitate wiring.

Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

Before connecting the thermostat check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.

Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring shown in figure 60. Use 18-gauge wire or larger that is suitable for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Na­ tional Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make-up box.

NOTE - The ML193UH furnace contains electronic compo­ nents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

Accessory Terminals

One line voltage “EAC” 1/4” spade terminal is provided on the furnace integrated control. See figure 1 for integrated control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an exter­ nal relay.

One line voltage “HUM” 1/4” spade terminal is provided on the furnace integrated control. See figure 1 for integrated control configuration. This terminal is energized in the heating mode when the combustion air inducer is operat­ ing. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con­ nected to one of the provided neutral terminals. If a humidi­ fier rated at greater than one amp is connected to this termi­ nal, it is necessary to use an external relay relay.

Thermostat

Install the room thermostat according to the instructions provided with the thermostat. See figure 60 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropri­ ate dual fuel thermostat instructions.

Indoor Blower Speeds

1 - When the thermostat is set to “FAN ON,” the indoor blower will run continuously on the heating speed when there is no cooling or heating demand.

2 - When the ML193UH is running in the heating mode, the indoor blower will run on the heating speed.

3 - When there is a cooling demand, the indoor blower will run on the cooling speed.

Page 37

Page 37
Image 37
Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge Electrical, Accessory Terminals