Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge, ML193UH

Models: Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge ML193UH

1 51
Download 51 pages 42.64 Kb
Page 7
Image 7
Air from Outside

Air from Outside

If air from outside is brought in for combustion and ventila­ tion, the confined space shall be provided with two perma­ nent openings. One opening shall be within 12” (305mm) of the top of the enclosure and one within 12” (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through verti­ cal ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rat­ ing of all equipment in the enclosure (See figure 5). It is also permissible to bring in air for combustion from a ventilated attic (figure 6) or ventilated crawl space (figure 7).

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(Inlet Air from Crawl Space and Outlet Air to Ouside)

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)

Roof Terminated

Exhaust Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Minimum

 

 

 

Ventilation

 

Furnace

 

 

 

 

 

 

 

 

 

 

 

 

12 in.(305mm)

 

 

 

Louvers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Above crawl

 

 

 

(Crawl space)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

space floor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coupling or

3 in. to 2 in. *Intake Debris Screen Provided)

Transition

ROOF TERMINATED EXHAUST PIPE

SIDE WALL

TERMINATED EXHAUST PIPE (ALTERNATE LOCATION)

VENTILATION LOUVERS

(Each end of attic)

OUTLET

AIR

FURNACE

 

VENTILATION

 

LOUVERS

INLET

(For unheated

AIR

crawl space)

(Field Provided)

* See table 6 for maximum vent lengths

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 7

If air from outside is brought in for combustion and ventila­ tion, the confined space must have two permanent open­ ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 5

EQUIPMENT IN CONFINED SPACE

(Inlet Air from Ventilated Attic and Outlet Air to Outside)

mm) of the bottom. These openings must communicate di­

rectly or by ducts with the outdoors or spaces (crawl or at­

tic) that freely communicate with the outdoors or indirectly

through vertical ducts. Each opening shall have a minimum

free area of 1 square inch (645 mm2) per 4,000 Btu (1.17

kW) per hour of total input rating of all equipment in the en­

closure. See figures 5 and 8. When communicating with

the outdoors through horizontal ducts, each opening shall

Roof Terminated

Exhaust Pipe

Ventilation Louvers

Inlet Air

(Minimum

12 in.(305mm) Above

attic floor)

*Intake Debris

Screen

(Provided)

have a minimum free area of 1 square inch (645 mm2) per

2,000 Btu (.56 kW) per total input rating of all equipment in

the enclosure. See figure 9.

When ducts are used, they shall be of the same cross-sec­ tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must

Furnace

* See table 6 for maximum vent lengths

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 6

be considered. If the design and free area of protective cov­ ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­ cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera­ tion.

Page 7

Page 7
Image 7
Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge, ML193UH Air from Outside