Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge Diameter

Models: Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge ML193UH

1 51
Download 51 pages 42.64 Kb
Page 23
Image 23
Winter Design

TABLE 7

Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For

Winter Design Temperatures Single - Stage High Efficiency Furnace

Winter Design

Vent Pipe

 

 

Unit Input Size

 

 

 

 

 

 

 

Temperatures1 °F (°C)

Diameter

045

070

090

110

135

 

 

PVC

PVC

PVC

PVC

PVC

 

 

 

 

 

 

 

32 to 21

2 in.

26

44

44

24

N/A

 

 

 

 

 

 

(0 to -6)

2-1/2 in.

18

32

50

58

N/A

 

 

 

 

 

 

 

 

3 in.

14

26

38

55

60

 

 

 

 

 

 

 

 

2 in

16

28

40

24

N/A

20 to 1

 

 

 

 

 

 

2-1/2 in.

12

20

30

44

N/A

(-7 to -17)

 

 

 

 

 

 

 

3 in.

9

16

26

32

40

 

 

 

 

 

 

 

 

2 in.

10

20

30

24

N/A

0 to -20

 

 

 

 

 

 

2-1/2 in.

8

14

20

32

N/A

(-18 to -29)

 

 

 

 

 

 

 

3 in.

4

10

16

26

30

 

 

 

 

 

 

 

1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.

NOTE - Maximum unisulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.

NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure32.

 

Conditioned

 

 

Space

 

 

 

Exhaust

 

Pipe Insulation

Pipe

 

 

Conditioned

 

Intake

Unconditioned

Pipe

Space

 

Space

 

 

 

FIGURE 32

Page 23

Page 23
Image 23
Lennox International Inc Lennox Merit Series Gas Furnace Upflow/Horizontal Air Discharge, ML193UH Winter Design, Vent Pipe