TABLE 7
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
Winter Design Temperatures Single - Stage High Efficiency Furnace
Winter Design | Vent Pipe |
|
| Unit Input Size |
|
| |
|
|
|
|
| |||
Temperatures1 °F (°C) | Diameter | 045 | 070 | 090 | 110 | 135 | |
|
| PVC | PVC | PVC | PVC | PVC | |
|
|
|
|
|
|
| |
32 to 21 | 2 in. | 26 | 44 | 44 | 24 | N/A | |
|
|
|
|
|
| ||
(0 to | 18 | 32 | 50 | 58 | N/A | ||
|
|
|
|
|
|
| |
| 3 in. | 14 | 26 | 38 | 55 | 60 | |
|
|
|
|
|
|
| |
| 2 in | 16 | 28 | 40 | 24 | N/A | |
20 to 1 |
|
|
|
|
|
| |
12 | 20 | 30 | 44 | N/A | |||
|
|
|
|
|
| ||
| 3 in. | 9 | 16 | 26 | 32 | 40 | |
|
|
|
|
|
|
| |
| 2 in. | 10 | 20 | 30 | 24 | N/A | |
0 to |
|
|
|
|
|
| |
8 | 14 | 20 | 32 | N/A | |||
|
|
|
|
|
| ||
| 3 in. | 4 | 10 | 16 | 26 | 30 | |
|
|
|
|
|
|
|
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
NOTE - Maximum unisulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure32.
| Conditioned |
|
| Space |
|
|
| Exhaust |
| Pipe Insulation | Pipe |
|
| |
Conditioned |
| Intake |
Unconditioned | Pipe | |
Space |
| |
Space |
| |
|
|
FIGURE 32
Page 23