6-3 Response to Abnormal Conditions

IEEE 1547 (Default)

Parameter

Range

Clearing Time (s)

 

V < 60V

< 0.16

Phase Voltage

60V ≤ V < 106V

< 2.00

132V ≤ V < 144V

< 1.00

 

 

V ≥ 144V

< 0.16 (< 0.016, Hawaii mode - TOV)1)

Frequency

> 60.5Hz

< 0.16

< 59.3Hz (< 57 Hz, Hawaii mode)1)

< 0.16

 

1)For setting to Hawaii mode, refer to Chapter 4-3. Configuring the Installation App - Step 5.

Note 1 : This test is performed in nominal conditions, except for test parameter.

Note 2 : After clearing, if grid returns to the normal state, it takes about 5 minutes for operation of the AC module.

6-4 Dedicated Cables

 

 

 

 

 

Trunk

 

 

Type

 

TC-ER sunlight resistant

Cable

Max. Voltage

 

600V

Max. Current

 

20A

 

 

 

Size

 

12AWG

Connector

Max. Voltage

 

300V

Max. Current

 

20A

 

 

 

 

Drop

 

 

Type

 

TC-ER sunlight resistant

Cable

Max. Voltage

 

600V

Max. Current

 

5A

 

 

 

Size

 

18AWG

Connector

Max. Voltage

 

300V

Max. Current

 

5A

 

 

 

 

Certification

 

 

UL9703, UL6703A

 

 

 

Dimensions

 

 

400 mm

 

 

(95.75 inch)

 

 

53 mm

31.5 mm

 

 

(2.09 inch)

(1.24 inch)

 

122 mm

 

 

 

(4.80 inch)

 

1,200 mm

66 mm

 

 

(47.24 inch)

(2.60 inch)

34

 

 

 