3-10 Connecting AC Module Array to Distribution Panel (General AC Cable, Transition Cable)

– 240VAC, 208VAC

Before connecting general AC cable from the AC junction box to distribution panel, adhere to the following items:

Notice

To prevent the danger of electric shock, check again if the circuit breaker is surely turned off.

LG does not provide separate general AC cables between AC junction box and the distribution panel.

Install using certified materials and system components.

Do not put in any liquid. There is a danger of electric shock.

Do not use any damaged cables.

Do not cut or transform the dedicated cables for use.

There is an extra wire in the transition cable. Do not use it.

The wire is blocked by a shrink tube at section of the outer jacket and works on shrink tubes must be done at the factory only.

Checking Accessory

L1

L2

Neutral

Male transition cable

Female transition cable

Neutral is a common conductor uses only for AC module voltage measurement reference. This conductor does not carry current under normal or abnormal conditions.

WARNING

To prevent property damage or danger to human life by fire or explosion, do not connect any consumable device between AC module and the circuit breaker.

To prevent the danger of the electric shock, make sure to turn off the circuit breaker.

Make sure to use the dedicated cable provided by LG Electronics. Outside parts may cause critical danger.

18

Page 18